Cylinder Type
HFRS 800kV/3200kVA Resonant Test System: Dual-Module Solution for Ultra High Voltage Testing
Dual-Module Configuration Specifications
Parameter | Single Module | Series Connection |
---|---|---|
Rated Voltage | 400kV | 800kV |
Rated Power | 1600kVar | 3200kVar |
Inductance | 318H ±2% | 636H ±2% |
Rated Current | 4A | 4A |
Withstand Voltage | 440kV | 880kV/1min |
Key Performance Characteristics
Frequency Range: 30-300Hz operational bandwidth
Quality Factor: Q≥60 at 50Hz
Thermal Performance:
Winding temperature rise: ≤80K
Transformer oil rise: ≤55K
Epoxy tube surface: ≤40K
Duty Cycle: 15 minutes ON / 1 hour OFF (4 cycles per day)
Advanced Engineering Features
Magnetic Circuit Design
Precision air-gapped iron core design
High-purity copper windings with ±2% tolerance
318H base inductance per module
Thermal Management System
Oil-immersed self-cooling with iron tank
Breather capsule for oil expansion control
Optimized heat dissipation channels
Field Deployment Advantages
Shock-resistant transport design (5G certified)
Integrated lifting hooks (8-ton capacity)
Dual-configuration nameplates
IP55-rated all-weather enclosure
Performance Comparison
Feature | HFRS Metal Tank | Standard Epoxy |
---|---|---|
Maximum Voltage | 880kV | Typically 650kV |
Heat Dissipation | 55K oil rise | 70K+ typical |
Transport Durability | 5G shock resistant | 2G limit |
Typical Applications
1. Ultra High Voltage Cable Testing
800kV AC withstand testing
Partial discharge measurement
2. EHV Transformer Testing
Winding deformation analysis
Lightning impulse simulation
3. GIS Field Commissioning
880kV withstand verification
Three-phase simultaneous testing
Operational Guidelines
Safety Protocols
Maintain 12m clearance during 800kV tests
Implement dual-point grounding
Maintenance Requirements
Monthly oil dielectric tests
Annual winding resistance checks