Cylinder Type
HFRS 600kV/6000kVA Resonant Test System: Technical Specifications & Field Applications
Modular Design Configuration
The HFRS system features a revolutionary dual-module design with flexible connection options:
Configuration | Voltage Rating | Capacitance | Inductance | Current Rating |
---|---|---|---|---|
Single Module | 300kV | 3000kVar | 95H | 10A |
Parallel Connection | 300kV | 6000kVar | 47.5H | 20A |
Series Connection | 600kV | 3000kVar | 190H | 10A |
Key Performance Parameters
Frequency Range: 20-300Hz operational bandwidth
Insulation Level: 330kV/1min (single module), 660kV/1min (dual module)
Thermal Performance:
Winding temperature rise: ≤80K
Transformer oil temperature rise: ≤55K
Epoxy tube surface rise: <40K
Duty Cycle:
Option 1: 15min ON / 1h OFF (4 cycles/day)
Option 2: 1h ON / 3h OFF (3 cycles/day)
Advanced Structural Features
Core Construction
The reactor utilizes an iron core with segmented air gaps and precision copper winding technology, delivering:
Superior magnetic flux control
Reduced eddy current losses
Enhanced thermal stability
Cooling System
Oil-immersed self-cooling design with:
Iron shell construction for optimal heat dissipation
Integrated breather capsule for oil expansion compensation
Military-grade epoxy insulation
Field Deployment Advantages
Engineered for demanding field applications:
Shock-resistant design for rail/road transport
Suspension hooks for easy installation
Dual-option nameplates (single/series configuration)
All-weather metal tank construction (superior to epoxy tube designs)
Comparative Advantages
Feature | Metal Tank Design | Epoxy Tube Design |
---|---|---|
Heat Dissipation | Excellent (55K max oil rise) | Moderate |
Transport Durability | Military-grade protection | Vulnerable to impacts |
Field Maintenance | Easy visual inspection | Limited access |
Environmental Resistance | IP54 standard | Typically IP42 |
Typical Applications
1. Power Cable Testing
Ideal for 220kV-500kV XLPE cable systems with:
Partial discharge measurement capability
Tan delta testing at full operating voltage
2. GIS Field Commissioning
Essential for gas-insulated substations:
660kV withstand voltage verification
SF6 equipment diagnostic testing
3. Transformer Manufacturing
Critical for quality assurance:
Lightning impulse simulation
Turn-to-turn insulation verification
Operational Guidelines
Safety Precautions
Maintain minimum 5m clearance during 600kV tests
Always discharge capacitance before handling
Monitor oil temperature during continuous operation
Maintenance Protocol
Quarterly oil dielectric strength tests
Annual winding resistance measurement
Breather capsule inspection every 6 months
This resonant test system represents the pinnacle of high voltage testing technology, combining unparalleled safety features with exceptional field performance for utility-scale applications.