Cylinder Type
HFRS 800kV/16MVA Resonant Test System: Four-Stage Modular Solution for Ultra High Voltage Testing
Modular Configuration Options
Configuration | Voltage | Power | Inductance | Current | Withstand |
---|---|---|---|---|---|
Single Reactor | 200kV | 4000kVar | 50H | 20A | 220kV/1min |
2-Series | 400kV | 8000kVar | 100H | 40A | 440kV/1min |
3-Series | 600kV | 12000kVar | 150H | 60A | 660kV/1min |
4-Series | 800kV | 16000kVar | 200H | 80A | 880kV/1min |
Key Performance Parameters
Frequency Range: 20-300Hz
Accuracy: <1% error
Quality Factor: Q≥40
Thermal Performance:
Winding temperature rise: ≤65K
Transformer oil rise: ≤55K
Epoxy tube surface: ≤40K
Duty Cycle: 30min ON / 60min OFF (max 3 cycles/day)
Advanced Structural Features
Modular Design
Four identical 200kV reactor modules
Mounted on 30kV insulated pedestal
Flexible series connection options
Core Technology
Segmented air gap iron core
High-purity copper windings
Precision inductance matching (±1%)
Cooling System
Oil-immersed self-cooling design
Epoxy cylinder structure
Integrated breather capsule
Field Deployment
Transport-optimized design (rail/road)
Integrated lifting hooks
Configuration-specific nameplates
Performance Advantages
Feature | HFRS System | Conventional Units |
---|---|---|
Maximum Voltage | 880kV | Typically 650kV |
Modular Flexibility | 4-stage configuration | Usually fixed |
Current Capacity | Up to 80A | Typically 40A max |
Typical Applications
1. UHV Equipment Testing
800kV+ transformer testing
GIS withstand verification
2. Long Cable Systems
Extra high voltage cable testing
Partial discharge measurement
3. Power Station Commissioning
Generator step-up transformer testing
Busbar system verification
Operational Guidelines
Safety Procedures
15m minimum clearance for 800kV tests
Strict grounding protocol during reconfiguration
Maintenance Schedule
Pre-test insulation verification
Quarterly oil analysis
Annual full system calibration