Cylinder Type
HFRS 500kV/2500kVA Modular Resonant System
The HFRS 500kV/2500kVA redefines testing flexibility with three operational configurations and future expansion to 750kV, delivering precision 250H±1% inductance in field conditions.
Multi-Configuration Operation
1. Series Mode (500kV)
Output: 500kV at 5A (2.5MVA)
Inductance: 250H precision
Withstand: 600kV for 60 seconds
2. Parallel Mode (250kV)
Output: 250kV at 10A (2.5MVA)
Inductance: 62.5H
Current Capacity: 2× rated output
3. Future Expansion (750kV)
Output: 750kV at 5A (3.75MVA)
Modules: 3 reactor configuration
Inductance: 375H
Precision Engineering
Parameter | Specification |
---|---|
Frequency Range | 30-300Hz |
Quality Factor | Q≥60 @50Hz |
Thermal Capacity | 4 cycles/day (1hr ON/1hr OFF) |
Temperature Limits |
|
Modular Design Advantages
Base Module Specifications
Rated Voltage: 250kV
Inductance: 125H precision
Cooling: Iron-shell oil immersion
Configuration Flexibility
Modules | Configuration | Output |
---|---|---|
2 | Series | 500kV/5A |
2 | Parallel | 250kV/10A |
3 | Series | 750kV/5A |
Military-Grade Construction
Enhanced Cooling System
Iron-shell oil tanks provide:
40% better cooling than epoxy
Natural convection efficiency<