Cylinder Type
HFRS 220kV/14520kVA Series Resonant Test System
Engineered for extra-high-voltage field testing, the HFRS 220kV/14520kVA system combines four series-connected reactors to deliver precision 10H±1% inductance with exceptional 264kV/1min voltage withstand capability.
High-Performance Specifications
Series Output: 220kV at 66A (14.52MVA)
Voltage Endurance: 264kV for 1 minute
Inductance Precision: 10H ±1%
Frequency Range: 20-300Hz
Precision Engineering
Core Parameters
Quality Factor: Q≥40-120
Thermal Performance:
80K maximum winding temperature
55K transformer oil limit
40K epoxy surface temperature
Duty Cycle: 1hr ON / 1hr OFF (max 3 cycles/day)
Series Connection Advantages
Feature | Benefit |
---|---|
30kV insulated pedestal | Secure series connection |
Four-reactor design | Distributed voltage stress |
Robust Construction
Mechanical Design
Epoxy cylinder structure provides:
Enhanced heat dissipation
Four reactors feature:
Copper lead-wire windings
Segmented iron core air gaps
Mechanical stability |
Transport Protection
Vibration-tested for:
2000km railway transport
1000km highway movement
220kV-rated lifting hooks
Certification & Compliance
Meets IEC 60060-1 insulation standards
Transport certified per IEC 61373