600kV ~ 800kV Range
LQHVF 800kV/800pF Dual-Stage Capacitive Voltage Divider & Coupling Capacitor
Engineered for precision high-voltage measurement in critical infrastructure, this dual-stage capacitive divider delivers laboratory-grade accuracy in field environments. With configurable 400kV/800kV operation and industry-leading <0.2% dielectric loss, it's ideal for substation testing and power system commissioning.
Core Technical Specifications
Parameter | Full System | Per Stage |
---|---|---|
Rated Voltage | 800kV | 400kV |
Configuration | 2-stage series connection | |
Total Capacitance | 800pF | - |
Stage Capacitance | - | 1600pF |
Dividing Ratio | 2000:1 | |
Measurement Accuracy | ≤±1% | |
Dielectric Loss | < 0.2% | |
Continuous Operation | 60 minutes @ 100% voltage | |
Insulation Withstand | 880kV (110%) for 60 seconds | |
Cooling System | ONAN (Oil Natural Air Natural) |
Advanced Dual-Stage Architecture
Single-Stage Mode
400kV operation
1600pF capacitance
Ideal for transformer testing
Dual-Stage Mode
800kV operation
800pF total capacitance
For GIS and transmission lines
Precision Measurement System
Special lead-wire for variable frequency power sources (30-300Hz)
Scalable corona-free HV connections
Automatic temperature compensation
Harmonic distortion immunity
Structural Advantages
Field-Optimized Design
Removable Aluminum Corona Rings: Detachable for compact transport
Stabilized Pedestal: Ensures level operation on uneven terrain
Modular Assembly: Quick stage connection/disconnection
ONAN Cooling: Maintains oil temperature <55°C at 800kV
Performance Validation
Test | Condition | Result |
---|---|---|
Dielectric Loss | 800kV @ 50Hz | <0.18% (average) |
Thermal Stability | 60 mins @ 800kV | ΔT <30K |
Voltage Withstand | 880kV for 60s | No flashover/corona |
Ratio Linearity | 200-800kV range | ±0.8% deviation |
Industry Applications
Power Substation Commissioning
800kV GIS testing with 2000:1 ratio for precise RMS measurement
Transformer Validation
Single-stage 400kV operation for factory acceptance tests
Research & Development
Configurable staging for high-voltage component testing
Compliance & Certifications
IEC 60060-1/2: High-voltage test techniques
IEEE 4: Standard for HV testing
IEC 60270: Partial discharge measurements
IEC 60137: Insulated bushings
Includes NIST-traceable calibration and 880kV withstand certification.
Field Operation Tip
When operating in single-stage mode, disconnect and ground unused stage to prevent capacitive coupling interference.
Ordering Information
Package includes: Two capacitor stages, aluminum corona rings, removable pedestal, VF-compatible measuring leads, and calibration documents. Request stage-configuration guide for optimal setup.