600kV ~ 800kV Range
LQHVF 800kV/630pF Capacitive Voltage Divider
Engineered for demanding variable-frequency high-voltage testing, this 800kV capacitive divider delivers precision measurements across 30-300Hz. With triple-unit modular design and ONAN cooling, it's ideal for cable testing, GIS commissioning, and renewable energy grid integration.
Core Technical Specifications
Parameter | Specification | Standard |
---|---|---|
Rated Voltage | 800kV | IEC 60060-1 |
Frequency Range | 30-300Hz | IEC 60076-16 |
Configuration | 3 units in series | - |
Total Capacitance | 630pF | IEC 60358 |
Single Unit Specs | 400kV / 1260pF | |
Dividing Ratio | 2000:1 | - |
Voltage Ratio Error | ≤1% (RMS) | IEC 60060-2 |
Measurement Accuracy | ≤±1.5% | IEEE 4 |
Dielectric Loss | < 0.5% | IEC 60247 |
Insulation Withstand | 880kV (110%) for 60s | IEC 62271 |
Cooling System | ONAN (Oil Natural Air Natural) | IEC 60502 |
Advanced Engineering Features
Triple-Unit Modular Design
Three 400kV/1260pF units in series
Transport-optimized disassembly/reassembly
Individual unit testing capability
Redundancy for critical operations
Wide-Frequency Operation
Maintains accuracy across 30-300Hz range for:
Cable resonant testing systems
VF power source compatibility
Harmonic-rich environments
Smart Measurement System
Special lead-wire to variable frequency power sources
Single-stage and two-stage serial voltage measurement
Scalable corona-free HV connections
Automatic temperature compensation
Structural Advantages
Field-Optimized Design
Removable Aluminum Corona Rings: Detachable for compact transport
Stabilized Pedestal: Ensures level operation on uneven terrain
ONAN Cooling: Maintains oil temperature <60°C at full load
Modular Assembly: Fits standard HV test trailers
Performance Validation
Test | Condition | Result |
---|---|---|
Frequency Response | 30-300Hz @ 800kV | Ratio error <1% |
Thermal Stability | 60 mins @ 100% load | ΔT <35K |
Dielectric Withstand | 880kV for 60s | No flashover |
Transport Simulation | IEC 60068-2-27 | Zero calibration shift |
Industry Applications
XLPE Cable Testing
Resonant testing at 30-300Hz with ±1.5% accuracy
GIS Commissioning
VF withstand testing up to 800kV
Offshore Wind Integration
Grid connection validation with variable frequency sources
Compliance & Certification
IEC 60060-1/2: High-voltage test techniques
IEEE 4: Standard for HV testing
IEC 60270: Partial discharge measurements
IEC 60502: Power cables accessories
Includes NIST-traceable calibration certificate and 880kV withstand test report.
Field Operation Tip
For resonant tests below 50Hz, allow 10-minute warm-up at 30% voltage to stabilize dielectric properties before full-power measurements.
Ordering Information
Package includes: Three capacitor units, aluminum corona rings, removable pedestal, VF-compatible measuring leads, and calibration documents. Request resonant test configuration guide.