600kV ~ 800kV Range
LQHVF 800kV/2000pF 4-Stage Modular Capacitive Voltage Divider
Engineered for maximum flexibility in high-voltage testing, this configurable 4-stage divider operates from 200kV to 800kV with laboratory-grade precision. Featuring 20-300Hz frequency range and NIST-traceable 8000:1 ratio calibration, it's ideal for utilities, test labs, and OEM validation.
Modular Stage Configuration
1 Stage → 2 Stages → 3 Stages → 4 Stages
200kV → 400kV → 600kV → 800kV
Core Technical Specifications
Parameter | Specification | Standard |
---|---|---|
Max Rated Voltage | 800kV (4 stages) | IEC 60060-1 |
Frequency Range | 20-300Hz | IEC 60076-16 |
Nominal Ratio | 8000:1 | NIST Certified |
Measurement Accuracy | ≤±1.5% | IEC 60060-2 |
Voltage Ratio Error | ≤1% (RMS) | - |
Dielectric Loss | < 0.2% | IEC 60247 |
Insulation Withstand | 880kV (110%) for 60s | IEEE 4 |
Cooling System | ONAN (Oil Natural Air Natural) | IEC 60502 |
Configurable Stage Operations
Single-Stage (200kV)
Capacitance: 8000pF
Applications: Transformer testing
Max Frequency: 300Hz
Dual-Stage (400kV)
Capacitance: 4000pF
Applications: Cable testing
Ideal for: Factory acceptance tests
Triple-Stage (600kV)
Capacitance: 2666pF
Applications: GIS commissioning
Special Feature: Partial discharge detection
Quad-Stage (800kV)
Capacitance: 2000pF
Applications: Transmission line testing
Withstand: 880kV for 60s
Advanced Measurement System
Precision Instrumentation
NIST-traceable 8000:1 ratio calibration
Special lead-wire for variable frequency sources (20-300Hz)
Automatic temperature compensation
Harmonic immunity up to 15th order
Structural Advantages
Field-Optimized Design
Removable Aluminum Corona Rings: Detachable for compact transport
Stabilized Pedestal: Ensures level operation on uneven terrain
Modular Assembly: Tool-free stage connection
ONAN Cooling: Maintains ΔT <30K at 800kV
Scalable Connections: Corona-free HV terminals
Performance Validation
Test | Condition | Result |
---|---|---|
Ratio Accuracy | Full 200-800kV range | ±1.2% maximum deviation |
Frequency Response | 20-300Hz @ 800kV | <0.8% error |
Thermal Stability | 60 mins @ 800kV | Oil ΔT <25K |
Transport Durability | IEC 60068-2-27 | Zero calibration shift |
Industry Applications
Utility Substations
800kV GIS commissioning with 8000:1 ratio
Cable Manufacturers
Resonant testing at 20-300Hz
Transformer Factories
200kV-400kV routine tests
Research Facilities
Configurable staging for component R&D
Compliance & Certifications
IEC 60060-1/2: High-voltage test techniques
IEEE 4: Standard for HV testing
IEC 60270: Partial discharge measurements
IEC 60502: Power cables accessories
NIST-traceable calibration certificate (8000:1 ratio)
Field Operation Tip
For low-frequency tests (20-50Hz), pre-heat oil to 30°C for optimal dielectric stability. Use single-stage configuration for frequencies >250Hz.
Ordering Information
Package includes: Four capacitor stages, aluminum corona rings, removable pedestal, VF-compatible measuring leads, NIST calibration certificate, and operation manual. Request stage-configuration guide for your application.