600kV ~ 800kV Range
LQHVF 800kV/500pF Dual-Stage Capacitive Divider & Coupling Capacitor
Engineered for critical high-voltage applications, this oil-immersed capacitive divider delivers precision measurement and coupling functions in a compact, field-deployable package. With industry-leading <5pC PD performance and 3000:1 ratio accuracy, it's ideal for substation testing and power system diagnostics.
Core Technical Specifications
Parameter | Per Stage | System (2 Stages) |
---|---|---|
Rated Voltage | 400kV | 800kV |
Frequency | 50Hz | |
Capacitance | 800pF | 1000pF |
Dividing Ratio | 3000:1 | |
Measurement Accuracy | ≤±1% | |
Dielectric Loss | <0.2% | |
Continuous Operation | 60 mins @ 800kV | |
Cooling System | ONAN (Oil Natural Air Natural) | |
Dimensions | Ø200mm × 7600mm (Corona ring Ø2500mm) | |
Weight | 600kg |
Advanced Partial Discharge Performance
100% Rated Voltage
<5pC PD level
Full system measurement
80% Rated Voltage
<3pC PD level
Ultra-sensitive detection
Innovative Structural Design
Modular Oil-Immersed Construction
Corona Rings: Ø2500mm aluminum alloy
LV Arm: Precision signal output
HV Arm: 800kV rated with corona-free design
Removable Base: Tool-free disassembly
Compact Field Deployment
Space-efficient Ø200mm profile
Vertical design: 7600mm height
Optimized for substation access
60% faster setup than conventional dividers
Dual-Function Operation
Precision Voltage Measurement
3000:1 dividing ratio
≤±1% accuracy
Harmonic immunity up to 2% THD
Coupling Capacitor for PD Testing
<5pC sensitivity at 800kV
IEC 60270 compliant
Whole-system measurement capability
Performance Validation
Test | Standard | Result |
---|---|---|
Thermal Stability | IEC 60502 | ΔT <25K @ 60min/800kV |
Partial Discharge | IEC 60270 | 4.2pC @ 800kV (average) |
Dielectric Loss | IEC 60247 | 0.18% @ 50Hz |
Mechanical Stability | IEC 60068-2-6 | Zero calibration shift |
Industry Applications
GIS Commissioning
800kV switchgear testing with <5pC PD sensitivity
Transformer Diagnostics
Dielectric loss measurement at 50Hz
Cable System Validation
Partial discharge mapping on HVDC cables
Research Laboratories
High-precision HV component testing
Field Deployment Advantages
Optimized for Challenging Sites
Compact Footprint: Ø200mm profile fits confined substations
Removable Design: 30-minute assembly by 2 technicians
All-Weather Operation: -30°C to +50°C range
Transport-Friendly: 600kg total weight
Compliance & Certification
IEC 60060-1/2: High-voltage test techniques
IEC 60270: Partial discharge measurements
IEEE 4: Standard for HV testing
IEC 60137: Insulated bushings
IEC 60502: Power cable accessories
Field Operation Tip
For maximum PD sensitivity, conduct baseline measurements at 80% voltage (640kV) where system achieves <3pC detection capability before proceeding to full 800kV tests.
Ordering Information
Package includes: HV/LV arms, removable base, aluminum corona rings (Ø2500mm), calibration certificate, and operation manual. Optional: PD measurement adapter kit, transport cradle, and field calibration set.