High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

600kV ~ 800kV Range

LQHVF 800kV/3000pF Wide-Frequency Capacitive Divider | HV Testing Solution

800kV capacitive voltage divider for 50-120Hz applications. Features 3000:1 ratio, <0.2% dielectric loss, ±1% accuracy, 880kV withstand, and ONAN cooling.


  • US$ 16,783.00
  • Lead time: 45 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHVF 800kV/3000pF Wide-Frequency Capacitive Voltage Divider

Engineered for precision high-voltage testing across power systems, this 50-120Hz capacitive divider delivers laboratory-grade accuracy in field environments. With 3000:1 ratio and modular design, it's ideal for generator testing, cable validation, and renewable energy applications.

Core Technical Specifications

ParameterSpecificationStandard
Rated Voltage800kVIEC 60060-1
Frequency Range50-120HzIEC 60076-16
Capacitance3000pFIEC 60358
Dividing Ratio3000:1-
Measurement Accuracy≤±1%IEC 60060-2
Dielectric Loss<0.2%IEC 60247
Insulation Withstand880kV for 60sIEEE 4
Cooling SystemONAN (Oil Natural Air Natural)IEC 60502

Frequency Response Performance

Maintains <0.8% ratio error across 50-120Hz range at 800kV

Advanced Engineering Features

Modular Connection System

  • Single-stage and two-stage serial measurement

  • Scalable corona-free HV connections

  • Special lead-wire for variable frequency power sources

  • Harmonic distortion immunity (up to 15th order)

Optimized Thermal Management

  • ONAN cooling maintains oil temperature <55°C

  • Natural convection for zero maintenance operation

  • Thermal stability across operating frequency range

Structural Design Advantages

Field-Optimized Components

  • Aluminum Corona Rings: Detachable design for compact transport

  • Removable Pedestal: Provides stability on uneven terrain

  • Scalable HV Bushings: Corona-free up to 880kV

  • Compact Connection Points: Tool-free assembly

Performance Validation

TestConditionResult
Frequency Response50-120Hz @ 800kV±0.75% max deviation
Thermal Stability60 mins @ 800kVOil ΔT <30K
Dielectric Withstand880kV for 60sNo flashover/corona
Transport SimulationIEC 60068-2-27Zero calibration shift

Industry Applications

Generator Testing

60-120Hz withstand testing for turbine generators

HVDC Cable Validation

50-120Hz resonant testing on XLPE cables

Renewable Integration

Wind farm step-up transformer commissioning

Research Laboratories

Frequency-dependent dielectric studies

Operational Advantages

Field Deployment Efficiency

  • Rapid Configuration: 30-minute setup by 2 technicians

  • All-Weather Operation: -25°C to +50°C range

  • No External Power: Passive ONAN cooling system

  • Minimal Maintenance: Sealed oil-immersed design

Compliance & Certifications

  • IEC 60060-1/2: High-voltage test techniques

  • IEEE 4: Standard for HV testing

  • IEC 60270: Partial discharge measurements

  • IEC 60502: Power cable accessories

  • IEC 60076: Power transformers

Field Operation Tip

For frequencies above 100Hz, reduce test duration to 30 minutes to maintain optimal dielectric stability and measurement accuracy.

Ordering Information

Package includes: Capacitive divider unit, aluminum corona rings, removable pedestal, VF-compatible measuring leads, calibration certificate. Optional: Frequency response report, transport cradle, and field verification kit.

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message