600kV ~ 800kV Range
LQHVF 720kV/2500pF Capacitive Voltage Divider & Coupling Capacitor
Engineered for precision in ultra-high-voltage systems, the LQHVF 720kV/2500pF dual-ratio capacitor delivers unmatched flexibility in measurement applications. Featuring switchable 2000:1 and 3600:1 outputs, this two-stage solution enables laboratory-grade accuracy in substation monitoring, transformer testing, and grid diagnostics at 50Hz operations.
Technical Specifications
Electrical Parameters
Rated Voltage: 720kV AC (2×360kV stages)
System Capacitance: 2500pF ±4%
Stage Capacitance: 5000pF per stage
Frequency: 50Hz
Performance Metrics
Dividing Ratios: 2000:1 & 3600:1 selectable
Accuracy: ≤±1% full scale
Dielectric Loss: <0.3%
Partial Discharge: ≤10pC at 720kV
Insulation Withstand: 792kV (110%) for 1min
Advanced Engineering Features
Dual-Ratio Measurement System
2000:1 for standard voltage measurement
3600:1 for high-sensitivity applications
Field-switchable without recalibration
Thermal & Dielectric Management
ONAN cooling (Oil Natural Air Natural)
Temperature stability: ±2°C at full load
N2-inerted oil preservation system
Precision Measurement Capabilities
Ratio | Application | Output Sensitivity |
---|---|---|
2000:1 | Standard voltage measurement | 360V at 720kV |
3600:1 | Partial discharge analysis | 200V at 720kV |
Partial Discharge Performance
≤10pC at 720kV (system verified)
Ultra-low noise measurement circuits
IEC 60270 compliant detection
Safety & Reliability Systems
Insulation Verification
792kV withstand for 60 seconds
Zero discharge during test protocol
Automatic PD cutoff at >10pC
Structural Integrity
Dual-stage seismic reinforcement
Corona-free HV connections
Removable transport components
Certifications & Industry Applications
International Standards
IEC 60060-1: High-voltage test techniques
IEC 60270: Partial discharge measurements
IEEE 4: Measurement standards
IEC 60358: Coupling capacitors
Critical Applications
EHV transformer ratio verification
Switchgear partial discharge mapping
HVDC converter station monitoring
Substation PLC communication
Operational Guidelines
Pre-test ratio selection calibration
Dual-grounding verification (IEC 61936)
Cooling system activation 30 minutes pre-energization
Continuous dielectric loss monitoring
Annual recertification per IEC 60480
Safety Notice: Requires Class E4 PPE per IEC 61482. Minimum clearance: 6.5 meters for 720kV operations.