600kV ~ 800kV Range
LQHVF 720kV/1000pF Capacitive Voltage Divider & Coupling Capacitor
Engineered for critical extra-high-voltage applications, the LQHVF 720kV/1000pF system delivers laboratory-grade precision in field conditions. Featuring an ultra-precise 3000:1 ratio and industry-leading ≤5pC partial discharge performance, this dual-function solution enables accurate voltage measurement and power line communication in demanding substation environments.
Technical Specifications
Electrical Parameters
Rated Voltage: 720kV AC
Capacitance: 1000pF ±4%
Frequency: 50Hz
Dividing Ratio: 3000:1 nominal
Performance Metrics
Accuracy: ≤±1% full scale
Dielectric Loss: <0.2%
Partial Discharge: ≤5pC at 720kV
Insulation Withstand: 792kV (110%) for 1min
Cooling System: ONAN (Oil Natural Air Natural)
Advanced Engineering Design
Transport-Optimized Components
Quick-release aluminum corona rings
Modular HV arm disassembly
Compact shipping configuration
N2-inerted oil preservation (O₂ <0.5%)
Precision Measurement System
3000:1 high-sensitivity ratio
Low-noise output (SNR >60dB)
Temperature-compensated electronics
Versatile Measurement Capabilities
Configuration | Voltage Range | Output Sensitivity |
---|---|---|
Single-Stage | 0-360kV | 120V at 360kV |
Two-Stage Series | 0-720kV | 240V at 720kV |
Connection System
Corona-free HV terminals (RIV <25dB)
Variable frequency source compatibility
Scalable connectors for GIS/transformer interfaces
Triple-shielded measuring leads
Stability & Safety Systems
Pedestal Design
Removable seismic-rated base
Interlocking stability mechanism
Ground-level measurement terminals
Dielectric Protection
Zero discharge at 792kV withstand test
Real-time PD monitoring system
Automatic de-energization on anomaly
Certifications & Industry Applications
International Standards
IEC 60060-1: High-voltage testing
IEC 60270: Partial discharge measurement
IEEE 4: Measurement standards
IEC 60358: Coupling capacitors
Critical Applications
EHV transformer diagnostic testing
Substation power line carrier communication
High-sensitivity partial discharge detection
Grid stability monitoring
Operational Guidelines
Pre-test insulation resistance verification (>10GΩ)
Dual-grounding confirmation (IEC 61936)
Cooling system activation 30 minutes pre-energization
Continuous PD monitoring during operation
Annual dielectric strength validation
Safety Notice: Requires Class E4 PPE per IEC 61482. Minimum clearance: 6.5 meters for 720kV operations.