600kV ~ 800kV Range
LQHVF 700kV/6000pF Capacitor Voltage Divider
Engineered for ultra-high-voltage testing environments, the LQHVF 700kV/6000pF capacitor voltage divider delivers laboratory-grade precision in field applications. Designed for power transmission verification, transformer testing, and switchgear validation, this dual-stage system operates at frequencies from 20-300Hz with exceptional stability.
Technical Specifications
Electrical Parameters
Rated Voltage: 700kV AC
Configuration: Two-stage (2×350kV)
Stage Capacitance: 12,000pF per stage
System Capacitance: 6,000pF
Frequency Range: 20-300Hz
Performance Metrics
Dividing Ratio: 7000:1 nominal
Ratio Error: ≤±1.5% (RMS)
Dielectric Loss: <0.5% @ 50Hz
Insulation Withstand: 770kV (110%) / 385kV per stage
Cooling System: ONAN (Oil Natural Air Natural)
Innovative Engineering Features
Modular Corona Suppression
Aluminum alloy corona rings optimized for 700kV+ operation
Quick-disassembly design for transport efficiency
Field-reconfigurable for single/dual-stage setups
Stabilized Pedestal System
Removable foundation with seismic-grade stability
Integrated vibration dampening
Ground-level measurement terminals
Advanced Measurement Capabilities
Operation Mode | Voltage Range | Configuration |
---|---|---|
Single-Stage | 0-350kV | Independent unit validation |
Dual-Stage Series | 0-700kV | Full-system testing |
Connection System
HV corona-free termination system
Scalable connectors for transformer/GIS interfaces
Low-inductance measuring leads (≤5nH/m)
Variable frequency power source compatibility
Certifications & Industry Applications
International Standards
IEC 60060-1: High-voltage test techniques
IEC 60270: Partial discharge measurement
IEEE C57.98: Dielectric loss guidelines
Critical Applications
Extra-high-voltage transformer commissioning
HVDC converter station testing
Cable system partial discharge analysis
Renewable energy substation diagnostics
Safety & Maintenance Protocols
Pre-energization dielectric verification (IEC 60480)
Dual-grounding check before testing
ONAN oil temperature monitoring (max 65°C)
Annual recalibration per ISO/IEC 17025
Safety Notice: Requires Class E4 PPE per IEC 61482 for operations >500kV. Minimum clearance: 5 meters.