600kV ~ 800kV Range
LQHVF 700kV/250pF High Voltage Measuring & Coupling Capacitor
Engineered for critical power infrastructure monitoring, the LQHVF 700kV/250pF dual-stage capacitor delivers laboratory-grade precision in substation environments. Combining ultra-low partial discharge performance with exceptional dielectric stability, this compact solution enables accurate voltage measurement and power line communication in extra-high-voltage networks.
Technical Specifications
Electrical Parameters
Rated Voltage: 700kV AC (2×350kV stages)
Stage Capacitance: 500pF ±5%
System Capacitance: 250pF +5%/-10%
Frequency: 50Hz
Performance Metrics
Partial Discharge:
≤3pC at 700kV (100% Un)
≤1pC at 560kV (80% Un)
Dielectric Loss: <0.2% @ 20°C
Short-Time Withstand: 840kV (1.2Un) for 60s
Compact Engineering Design
Space-Optimized Structure
Dimensions: 2000×2000×6400mm
Weight: 280kg
Dual-stage vertical integration
Minimal footprint for substation installation
Dielectric Performance
Stabilized tanδ (0.9-1.1 Uns)
Temperature-compensated design
N2-inerted insulation system
Precision Measurement Capabilities
Parameter | Value | Industry Benchmark |
---|---|---|
Partial Discharge @ 80% Un | ≤1pC | 5-10pC (typical) |
Voltage Withstand | 840kV/60s | 770kV/60s (IEC standard) |
Dielectric Stability | tanδ <0.2% | 0.3-0.5% (comparable units) |
Safety & Industry Applications
Ultra-Low PD Advantages
Early detection of insulation degradation
Reduced electromagnetic interference
Enhanced grid communication clarity
Critical Applications
EHV substation busbar monitoring
Power line carrier communication
Transformer diagnostic systems
Smart grid sensor networks
Certifications & Standards
International Compliance
IEC 60358-1: Coupling capacitors
IEC 60270: Partial discharge measurement
IEEE 4: Standard for HV testing
ANSI C93.1: Power line carrier requirements
Installation & Maintenance
Foundation preparation: 2.5×2.5m concrete pad
Stage assembly verification (torque 120Nm)
Pre-commissioning PD baseline test
Bi-annual dielectric loss monitoring
Safety Notice: Requires Class E3 PPE per IEC 61482. Minimum phase-to-ground clearance: 5 meters.