600kV ~ 800kV Range
LQHVF 700kV/2500pF Coupling Capacitor & Capacitive Voltage Divider
Engineered for precision across diverse testing scenarios, the LQHVF 700kV/2500pF system combines dual-ratio voltage measurement and coupling functions in a single, field-configurable unit. Designed for resonant testing facilities, power grid monitoring, and HV laboratory applications, this wideband solution operates from 20-300Hz with laboratory-grade accuracy and robust thermal management.
Technical Specifications
Electrical Parameters
Rated Voltage: 700kV AC
System Capacitance: 2500pF ±5%
Stage Configuration: 2×350kV (5000pF per stage)
Frequency Range: 20-300Hz
Performance Metrics
Dividing Ratios: 1000:1 & 2000:1 selectable
Accuracy: ≤±1% full scale
Dielectric Loss: <0.3%
Partial Discharge: ≤5pC at 700kV
Insulation Withstand: 770kV (110%) for 1min
Advanced Engineering Design
Modular Transport System
Quick-release aluminum corona rings
Stage-separable construction (2×350kV units)
Compact shipping dimensions
N2-inerted oil preservation (O₂ <0.5%)
Thermal & Frequency Performance
ONAN cooling with ±2°C stability
Wideband capacitance stability (±2% 20-300Hz)
Low-inductance design (≤8nH)
Versatile Measurement System
Configuration | Voltage Range | Optimal Ratio |
---|---|---|
Single-Stage | 0-350kV | 1000:1 |
Dual-Stage Series | 0-700kV | 2000:1 |
Connection System
Corona-free HV terminals (RIV <28dB)
Variable frequency source integration (20-300Hz)
Scalable connectors for GIS/bushing interfaces
Triple-shielded measuring leads
Stability & Safety Systems
Pedestal Design
Removable seismic-rated base (IEC 60068-3 Class 2)
Ground-level measurement terminals
Interlocking stability feet
Dielectric Protection
Zero discharge at 770kV withstand test
Automatic PD cutoff at >5pC
Real-time oil quality monitoring
Certifications & Industry Applications
International Standards
IEC 60060-1: High-voltage testing
IEC 60270: Partial discharge measurement
IEEE 4: Measurement techniques
IEC 60358: Coupling capacitors
Critical Applications
Resonant test systems for transformers
EHV cable partial discharge mapping
HVDC converter station diagnostics
Substation PLC communication
Operational Guidelines
Pre-test frequency calibration (20-300Hz sweep)
Dual-grounding verification (IEC 61936)
Cooling system activation 30 minutes pre-energization
Continuous dielectric loss monitoring
Annual recertification per IEC 60480
Safety Notice: Requires Class E4 PPE per IEC 61482. Minimum clearance: 6.5 meters for 700kV operations.