600kV ~ 800kV Range
LQHVF 700kV/1150pF Capacitive Voltage Divider & Coupling Capacitor
Engineered for precision across diverse frequency ranges, the LQHVF 700kV/1150pF system combines voltage measurement and coupling functions in a single, field-configurable unit. Designed for resonant testing, power quality analysis, and grid communication, this wideband solution operates from 25-300Hz with laboratory-grade accuracy and robust thermal management.
Technical Specifications
Electrical Parameters
Rated Voltage: 700kV AC
Capacitance: 1150pF ±4%
Frequency Range: 25-300Hz
Dividing Ratio: 2000:1 nominal
Performance Metrics
Voltage Ratio Error: ≤±1% (RMS)
Accuracy: ≤±1.5% full scale
Dielectric Loss: <0.5%
Insulation Withstand: 770kV (110%) for 60s
Advanced Engineering Features
Transport-Optimized System
Quick-release aluminum corona rings
Modular HV arm disassembly
Compact shipping configuration
N2-inerted oil preservation
Thermal & Frequency Management
ONAN cooling with ±3°C stability
Wideband capacitance linearity (25-300Hz)
Low-inductance internal design (≤10nH)
Versatile Measurement System
Connection Mode | Configuration | Frequency Optimization |
---|---|---|
Single-Stage | 0-700kV measurement | 25-300Hz full range |
Two-Stage Series | 0-1400kV equivalent | 50-150Hz optimal |
Connection System
Corona-free HV terminals (RIV <25dB)
Variable frequency source integration
Scalable connectors for GIS/transformer interfaces
Low-noise measuring leads (shielded triple-core)
Stability & Safety Systems
Pedestal Design
Removable seismic-rated base (IEC 60068-3)
Ground-level measurement terminals
Anti-tip locking mechanism
Dielectric Protection
Zero discharge at 770kV withstand test
Automatic PD cutoff at >5pC
Oil quality monitoring sensors
Certifications & Industry Applications
International Standards
IEC 60060-1: High-voltage testing
IEC 60270: Partial discharge
IEEE 4: Measurement techniques
IEC 60358: Coupling capacitors
Critical Applications
Resonant test systems for cables
Power factor correction monitoring
HVDC filter bank diagnostics
Substation PLC communication
Operational Guidelines
Pre-test frequency sweep calibration (25-300Hz)
Dual-grounding verification (IEC 61936)
ONAN cooling activation 30 minutes pre-energization
Real-time dielectric loss monitoring
Safety Notice: Requires Class E4 PPE per IEC 61482 for all operations. Minimum clearance: 6 meters.