Primary Switchgear Cabinet
LQPSC 0.415KV/2000A Primary Switchgear Cabinet
Industrial-grade power distribution solution designed for heavy-current applications requiring 2000A capacity with integrated monitoring and protection systems.
Technical Specifications
Model: LQPSC 0.415KV/2000A
Rated Frequency: 50Hz
Rated Voltage: 0.415kV (415V AC)
Rated Current: 2000A
Short-Time Current: 16kA (1-second withstand)
Protection Rating: IP20
Operation Time Delay: 5s
Control Voltage: 220V AC (switching operations)
Mechanical Endurance: 20,000 operations
Control Panel Features
Monitoring Instruments
Digital voltmeter (0-500V AC range)
Digital ammeter (0-2500A AC range)
Visual Indicators
Power supply switch-on indicator lamp (green)
Power supply switch-off indicator lamp (red)
Control Functions
Local/remote function selector switch
Emergency stop button
Key-operated control transfer
Core Functional Capabilities
High-Current Distribution: 2000A continuous rating
Short-Circuit Protection: 16kA withstand capacity
Time-Delayed Operation: 5-second adjustable delay
Dual Control Modes: Local and remote operation
Real-Time Monitoring: Voltage and current measurement
Status Indication: Visual confirmation of switch position
Protection System
Protection Type | Specification |
---|---|
Short-Circuit Withstand | 16kA for 1 second |
Overload Capacity | 150% In for 30 seconds |
Coordination Delay | Adjustable 0-5s time delay |
Arc Containment | Internal arc classification IAC AFL |
Industrial Applications
Steel manufacturing power distribution
Industrial plant main switchboards
Large-scale data center power systems
Mining operations power management
Industrial furnace control systems
Design & Construction
Enclosure: 3mm galvanized steel with powder coating
Busbar System: Silver-plated copper with 2500A rating
Thermal Management:
Forced-air ventilation with filters
Temperature monitoring sensors
Component Layout:
Segregated compartments for safety
Front-accessible components
Cable Management:
Bottom entry with cable gland plates
4×400mm² cable capacity per phase
Installation Requirements
Parameter | Specification |
---|---|
Mounting | Floor-standing with M20 anchor bolts |
Clearances | Front: 1200mm, Rear: 600mm, Sides: 300mm |
Ambient Temperature | -5°C to +40°C |
Relative Humidity | ≤95% RH (non-condensing) |
Foundation | Level concrete base ≥150mm thickness |
Operation & Maintenance
Switching Procedure
Verify instruments show normal parameters
Select local/remote operation mode
Initiate switching command
Confirm status lamp indication
Monitor meters during operation
Maintenance Protocol
Monthly:
Visual inspection of control panel
Verify indicator lamp functionality
Quarterly:
Calibrate meters and instruments
Busbar connection torque check
Biannual:
Insulation resistance test (min 1MΩ)
Time delay function verification
Annual:
Contact resistance measurement
Full operational sequence test
5-Year:
Comprehensive system overhaul
Protective device calibration
Compliance Standards
IEC 61439-1: Low-voltage switchgear assemblies
IEC 62271-200: AC metal-enclosed switchgear
IEC 60529: IP degree of protection
IEEE C37.20.1: Metal-enclosed low-voltage switchgear
ISO 9001:2015 Quality Management Systems
Certified for industrial power distribution in demanding environments requiring high-current capacity and reliable protection systems.