LQPSC 0.4KV/1875A Primary Switchgear Cabinet
High-capacity power distribution solution designed for industrial applications requiring 1875A current handling with 25kA short-circuit protection and comprehensive monitoring capabilities.
Technical Specifications
Model: LQPSC 0.4KV/1875A
Rated Frequency: 50Hz
Rated Voltage: 0.4kV (400V AC)
Rated Current: 1875A
Short-Time Current: 25kA
Protection Rating: IP20 (finger-safe design)
Operation Time Delay: 5s
Control Voltage: 220V AC (switching operations)
Mechanical Endurance: 10,000 operations
Installation: Indoor use
Control Panel Features
Monitoring Instruments:
Voltmeter for phase-to-phase voltage measurement
Ammeter for current load monitoring
Visual Indicators:
Power supply switch-on indicator lamp
Power supply switch-off indicator lamp
Control Functions:
Remote function selector switch
Local/remote operation mode
Core Functional Capabilities
High-Current Distribution: 1875A continuous rating
Short-Circuit Protection: 25kA withstand capacity
Delayed Operation: 5-second time delay for protection coordination
Dual Control Modes: Local and remote operation
Real-Time Monitoring: Voltage and current measurement
Protection System Details
Parameter | Specification |
---|---|
Short-Circuit Withstand | 25kA for 1 second |
Overload Capacity | 150% of rated current for 30 seconds |
Protection Coordination | 5-second adjustable time delay |
Arc Containment | Internal arc classification: IAC AFLR |
Industrial Applications
Steel manufacturing power distribution
Industrial plant main switchboards
Data center high-density power systems
Large-scale industrial motor control
Foundry and smelting operations
Design & Construction
Robust Enclosure: 3mm powder-coated steel
Thermal Management: Forced-air ventilation with filters
Busbar System: Tin-plated copper with 2500A rating
Component Layout: Segregated compartments for safety
Cable Management: Bottom entry with 4×200mm² cable capacity
Installation Requirements
Mounting: Floor-standing with M20 anchor bolts
Clearances:
Front: 1200mm minimum
Rear: 500mm minimum
Sides: 300mm minimum
Environmental Conditions:
Temperature: 0°C to +45°C
Humidity: ≤90% RH (non-condensing)
Altitude: ≤2000m ASL
Power Connections: 4× 500mm² per phase
Maintenance Protocol
Monthly:
Visual inspection of instruments and lamps
Verify control voltage stability
Quarterly:
Calibration check of meters
Busbar connection torque verification
Biannual:
Insulation resistance test (min 1MΩ)
Time delay function verification
Annual:
Full protection relay testing
Contact resistance measurement
Compliance Standards
IEC 61439-1: Low-voltage switchgear assemblies
IEC 62271-200: AC metal-enclosed switchgear
IEC 60529: IP degree of protection
IEEE C37.20: Switchgear standards