Primary Switchgear Cabinet
LQPGL -0.4kV/630A Single-Phase Primary Switchgear Cabinet
Shielded indoor switchgear solution featuring 20,000-operation durability and comprehensive protection functions for critical power distribution applications.
Core Technical Specifications
Phase Configuration: Single-phase
Rated Frequency: 50Hz
Rated Voltage: 0.4kV (400V AC)
Rated Current: 630A
Transient Current Rating: 16kA
Control Voltage: AC220V (switching operations)
Mechanical Endurance: 20,000 operations
Installation Environment: Indoor use only
Enclosure: Electromagnetic shielded design
Primary Functions
Electrical Isolation: Physical circuit separation capability
Remote Operation: Switch-on/off via control signals
Protection Systems:
Over-voltage protection
Over-current protection
Measurement & Indication: Real-time electrical parameter monitoring
Key Components
Instrument Transformers:
Current transformers (CTs)
Voltage transformers (VTs)
Switching Devices:
AC contactors
Grounding switches
Protection Relays:
Current relays
Voltage relays
Intermediate (auxiliary) relays
Control Interface:
Operation buttons
Status indicator lamps
Shielded Enclosure Features
EMI/RFI electromagnetic shielding
Corrosion-resistant coated steel
Touch-safe design per IEC 61439
Ventilation with particulate filters
Grounding continuity assurance
Industrial Applications
Commercial building main distribution panels
Data center power distribution units
Laboratory critical power systems
Hospital electrical infrastructure
Indoor industrial substations
Installation Requirements
Parameter | Specification |
---|---|
Ambient Temperature | +5°C to +40°C |
Relative Humidity | ≤85% (non-condensing) |
Altitude | ≤2000m ASL |
Vibration Tolerance | ≤0.3g acceleration |
Clearance Space | 800mm front access minimum |
Protection Coordination
16kA transient current withstand (3-cycle)
Over-voltage threshold: 110% of rated voltage
Over-current tripping: 125% of rated current
Ground fault detection: 10% imbalance sensitivity
Arc-flash mitigation design
Maintenance Protocol
Monthly: Visual inspection of indicators and contacts
Quarterly: Relay functional testing
Biannual:
Contact resistance measurement
Shielding integrity verification
Annual:
Dielectric strength test (2.5kV AC)
Protection relay calibration
Compliance Standards
IEC 61439: Low-voltage switchgear assemblies
IEC 62271: High-voltage switchgear standards
IEEE C37.20: Indoor switchgear requirements
EMC Directive 2014/30/EU
Certified for indoor electrical distribution in commercial and light industrial environments.