100kVA ~ 200kVA Range
LQLVF 200KVA/2*66.6A Power Noise Filter: High-Voltage EMI Suppression for Industrial Systems
Premium Noise Attenuation Performance
Engineered for critical EMI suppression in 3kV power distribution systems:
40KHz-100KHz range: >40dB attenuation
100KHz-1MHz range: >60dB attenuation
Background partial discharge: <5pC (per IEC 60270)
Filter reactor quality factor: >70
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 200KVA |
Rated Voltage | 3kV |
Current Rating | 2 × 33.3A (66.6A total) |
Frequency | 50Hz |
Insulation Level | 10kV/1min withstand (no abnormal discharge) |
Continuous Operation | 20 min at 100% rated load |
High-Voltage Insulation System
Robust protection for 3kV applications:
10kV/1min dielectric strength (exceeds IEC 60664 requirements)
Triple-layer epoxy resin encapsulation
Creepage distance: ≥30mm/kV
Corona-free design up to 4kV operational voltage
Partial discharge inception voltage >3.5kV
Advanced Filter Reactor Technology
High-performance components for superior EMI suppression:
Quality factor >70 for precise frequency targeting
Grain-oriented silicon steel core
Vacuum pressure impregnated windings
Embedded RTD sensors for temperature monitoring
Frequency-stable design (±0.5% over load range)
Industrial Applications
Ideal for 3kV systems in:
Industrial HV switchgear
Mine power distribution systems
Railway traction substations
High-voltage laboratory equipment
Renewable energy converter stations
OEM industrial machinery
Dual-Circuit Design Advantages
Enhanced system reliability and flexibility:
Independent circuits for critical redundancy
Asymmetric load balancing capability
Individual circuit monitoring points
Fault isolation protection per circuit
Parallel operation for higher current applications
Installation & Maintenance Protocol
Ensure optimal performance in high-voltage applications:
Maintain minimum 100mm clearance to grounded surfaces
Use silicone-insulated HV cable (12kV rating minimum)
Perform annual power factor/dissipation factor tests
Verify torque values on HV terminals (45 N·m ±3%)
Conduct partial discharge scans every 6 months
Calibrate monitoring sensors annually
Safety & Protection Features
Engineered for reliable operation in demanding environments:
Arc-resistant containment barriers
Over-temperature protection (Class F insulation system)
Automatic discharge circuit for capacitor banks
Surge protection (10kV/20μs withstand)
IP55-rated enclosure for dust/moisture protection
Compliance & Standards
Meets international requirements including:
IEC 61000-3-12 harmonic emissions
IEEE 519-2022 harmonic control
EN 62271-200 HV switchgear standards
IEC 60076-6 power reactor requirements
ANSI/IEEE C57.12.90 test code
For high-voltage applications or custom configurations, contact our specialized engineering team. Performance validated per IEC 61000-4-7 measurement standards.