Oil Testing Instrument
LQHV-640 Insulating Oil Dielectric Loss Tester
Precision analyzer for tan δ and DC resistivity of transformer oils with medium-frequency heating technology
Product Parameters
Technical Parameters
| Test voltage range | 0~2000VAC,0~500VDC |
| Test temperature range | at room temperature~120℃ |
| Dielectric loss test range | 0.00001~100 |
| Resistivity measurement range | 2.5MΩ·m~100TΩ·m |
| Relative capacitivity test range | 0~40 |
| Test capacitance range | 50pF ~ 200pF |
| Measurement accuracy - dielectric loss factor | ±(value×0.5%+0.0001) |
| Capacitance | ±(value×0.5%+0.1pF) |
| Relative capacitivity | ±10% indicates value |
| DC resistivity | ± (value ×0.5%+0.1) |
| Dielectric loss value resolution | 0.00001 |
| Resistivity resolution | 0.001MΩ·m |
| Capacitance resolution | 0.01pF |
| Relative capacitivity | 0.001 |
| Power | 500W |
| Dimensions | 470×425×385mm3 |
| Weight | 22kg |
Conditions Of Use
| Environment temperature | 0℃ ~ +40℃ |
| Relative humidity | ≤75%RH |
Compliant with: GB/T5654-2007 | IEC 60247 | ASTM D924
Key Advantages
⚡ 3-Electrode Structure – Eliminates stray capacitance errors (2mm gap precision)
⚡ Medium-Frequency Heating – Uniform temperature control (±0.5°C accuracy)
⚡ Dual-Parameter Testing – Measures both tan δ (0.0001-1) and resistivity (106-1016Ω·m)
⚡ Lab-to-Field Ready – 15kg portable design with 100-data memory
Testing Workflow
Sample Preparation – Oil filtration per IEC 60296
Auto-Calibration – Empty cup baseline correction
Precise Heating – Ramp to set temp (typically 90°C)
Dual Measurement:
Tan δ at 50Hz AC
DC resistivity (1kV polarization index)
Data Output – Touchscreen display + thermal print
Intelligent Safety Systems
🔒 Auto High-Voltage Cutoff – Triggers on open cover detection
🔒 Electrode Short-Circuit Protection
🔒 Temperature Limiter – Prevents overheating
Diagnostic Applications
Condition Monitoring
Detects oil oxidation (tan δ > 0.01 indicates aging)
Identifies moisture ingress (resistivity drop)
Quality Control
New oil acceptance testing
Regenerated oil validation
Why Choose LQHV-640?
| Feature | LQHV-640 | Conventional Bridge Methods |
|---|---|---|
| Test Speed | 8 minutes/sample | 25+ minutes |
| Temperature Stability | ±0.5°C | ±2°C |
Maintenance Protocol
🧼 Post-Test: Clean electrodes with n-heptane
📅 Quarterly: Verify calibration with reference oil
💾 Data Backup: Export stored results via USB