HTRS120kV/1500kVA Inductance Resonant Reactor for High Voltage Cable Testing

Product Overview

The HTRS120kV/1500kVA tank-type single-phase resonant reactor is designed for precision testing of power cables up to 35kV class. With three configurable output taps (120kV/75kV/50kV), this indoor-use equipment meets international standards for partial discharge testing and withstand voltage tests.

Technical Specifications

ParameterTap 1Tap 2Tap 3
Rated Output Voltage120kV75kV50kV
Rated Output Current12.5A20A30A
Cable Testing Capacity26/35kV cables (100-1000m)21/35kV cables (120-2400m)6/10kV to 12/20kV cables (110-3500m)
Inductance Adjustment Range25H~587H10H~200H4.6H~94H
Capacitor Load Range0.012μF~0.28μF0.035μF~0.70μF0.075μF~1.5μF

Key Features

1. Multi-Tap Design

  • Three voltage configurations for diverse testing requirements

  • Automatic inductance matching through coil gap adjustment

  • 1500kVA consistent capacity across all voltage levels

2. Advanced Insulation System

  • 25# transformer oil insulation (110kV level)

  • Partial discharge level ≤2pC at 120kV

  • Double epoxy tube construction with stainless steel brackets

3. Thermal Management

  • ONAN cooling method (Oil Natural Air Natural)

  • Winding temperature rise ≤65K at 50% rated load

  • Oil temperature rise ≤55K during 1-hour operation

Structural Design

External Construction

  • Tank-type housing with impact-resistant sky blue coating

  • 20kPa pressure tested flange connections

  • Aviation-grade acrylate sealing rings

Internal Components

  • 1Ni18T9 non-magnetic stainless steel guide rails

  • Double lead screw mechanism for noise reduction

  • Eddy current-optimized iron core structure

Typical Applications

This resonant reactor is ideal for:

  1. Factory acceptance tests (FAT) for 6kV-35kV power cables

  2. Partial discharge measurement systems

  3. Frequency withstand voltage tests per IEC 60840 standards

  4. High-capacity cable network commissioning

Quality Assurance

  • Total harmonic distortion within -20°~+40° range

  • Quality factor maintained at 20-100

  • Thermal expansion compensation design

Conclusion

The HTRS120kV/1500kVA resonant reactor provides a reliable solution for high-voltage cable testing across multiple voltage classes. Its innovative design ensures precise measurements while meeting stringent safety requirements for partial discharge and thermal performance in demanding electrical testing environments.