Tank Type
HTRS 350kV/8750kVA Dual-Voltage Resonant Test System
Dual-Voltage Configuration
Parameter | 350kV Mode | 250kV Mode |
---|---|---|
Rated Voltage | 350kV | 250kV |
Maximum Voltage | 385kV | 275kV |
Rated Current | 25A | 25A |
Inductance Range | 46.1H-1020H | 24.7H-400H |
Load Range | 0.00995μF-0.22μF | 0.0255μF-0.41μF |
Performance Characteristics
Extended Operation:
1 hour ON/3 hours OFF at 100% rating
20-day continuous at 2/3 voltage & 1/3 current
Ultra-Low PD: <2pC at 350kV
Quality Factor: ≥40 (full load), ≥50 (no load)
Precision Control: ±1% linearity across reactance range
Safety & Durability
Test | Condition | Requirement |
---|---|---|
Overcurrent | 110% (27.5A) | 300 seconds |
Overvoltage | 110% (385kV) | 60 seconds |
Discharge | 5× at 90% voltage | No damage |
Mechanical Design
Core Technology
Precision adjustable iron coil with:
22:1 inductance adjustment ratio
Dual epoxy resin insulation
Advanced eddy-current prevention:
1Ni18T9 non-magnetic stainless steel
Double lead screw mechanism
Enclosure System
Tank-type construction with:
20kPa pressure-rated seals
Aeronautical acrylate gaskets
Thermal management:
ONAN cooling
ΔT ≤65K (winding), ≤55K (oil)
Standards Compliance
International:
IEC 60-1 (High Voltage Testing)
IEC 1000 (EMC)
National:
GB 1094 (Reactor)
GB/T 1094.10-2004 (Acoustics)
Typical Applications
Ultra High Voltage (UHV) cable testing
500kV class transformer diagnostics
GIS partial discharge measurement
High-capacity capacitor bank validation
Quality Assurance
Factory testing includes:
72-hour heat run test
Partial discharge calibration
Lightning impulse verification
3-year warranty on core components