Tank Type
HTRS 250kV/4000kVA High-Frequency Resonant Reactor
Electrical Parameters
Parameter | Specification |
---|---|
Rated Capacity | 4000kVA |
Output Voltage | 20kV |
Output Current | 100A (5A-100A adjustable) |
Frequency | 115Hz ±1% |
Reactance Range | 0.2769H - 5.538H |
Load Capacitance | 346.2nF - 6924nF |
Performance Characteristics
Precision Waveform: ≤1% deviation
Ultra-Low Noise: <70dB at rated load
Quality Factor: ≥40 (typical)
Partial Discharge: <5pC at 100% UH
Impedance Range: 0.2kΩ - 4kΩ
Safety & Protection
Capability | Condition | Duration |
---|---|---|
Overcurrent | 120% In | 180 seconds |
Overvoltage | 110% (22kV) | 60 seconds |
Insulation | LV to Ground | 5kV/1min |
Mechanical Design
Core Technology
Adjustable iron coil structure with:
Precision gap control mechanism
Double epoxy resin insulation
Special 1Ni18T9 stainless steel components:
Non-magnetic guide rails
Dual lead screw adjustment system
Enclosure System
Tank-type construction with:
Military-grade acrylate seals
20kPa pressure rating
Sky blue corrosion-resistant coating
ONAN cooling with:
China GB 2536 #25 transformer oil
Thermal expansion compensation
Operational Parameters
Duty Cycle
Rated Load: 60 minutes continuous
Derated Operation: Unlimited at 80% rating
Thermal Limits
Winding temperature rise: ≤65K
Oil temperature rise: ≤55K
Typical Applications
High-frequency cable testing
Power transformer diagnostics
Industrial HV component validation
Research lab frequency testing
Quality Assurance
Factory testing includes:
Full-load endurance testing
Partial discharge calibration
Thermal imaging verification
Complies with:
IEC 60076 (Power Transformers)
GB 1094 (Chinese National Standard)