Tank Type
HTRS 250kV/5000kVA Multi-Tap Resonant Test System
Electrically Switched Voltage Configuration
Voltage Tap | Current | Inductance Range | Load Range |
---|---|---|---|
100kV | 20A | 6.37H-63.7H | 159nF-1592nF |
200kV | 20A | 25.5H-255H | 39.8nF-398nF |
250kV | 20A | 39.8H-398H | 25.5nF-255nF |
Key Performance Specifications
Ultra-Low PD:
<5pC at 250kV (100%)
<2pC at 200kV (80%)
Precision Waveform: ≤1.5% deviation
Exceptional Q Factor: ≥40
Noise Level: ≤75dB at full load
Safety & Durability Tests
Test | Condition | Requirement |
---|---|---|
Overcurrent | 120% rated current | 300 seconds operation |
Dielectric | HV winding | 275kV/1min withstand |
Pressure | Oil pillow | 50kPa for 24 hours |
Advanced Mechanical Design
Core Components
High-permeability D0130-30 silicon steel core
Four-output HV winding system:
10kV lotus-style external bushings
Motorized tap switching mechanism
Epoxy-insulated stainless steel structure:
Eddy current loss prevention
Thermal expansion compensation
Sealing System
Aeronautical-grade fluorine rubber seals:
Hardness: 70 Shore A
Tensile strength: ≥12MPa
Oil-resistant (25# transformer oil)
Machined base with stress-relief treatment
Thermal Management
Operational Limits:
1 hour continuous at 100% rating
Unlimited at 80% rating
Temperature Rise:
Winding: ≤65K
Oil: ≤55K
Typical Applications
EHV transformer frequency testing
High-capacity cable resonant verification
GIS partial discharge measurement
Industrial HV component validation
Quality Assurance
Factory testing includes:
Lightning impulse tests
Partial discharge calibration
Thermal imaging verification
Complies with:
GB 1094 (Power Transformers)
IEC 60270 (Partial Discharge)