Tank Type
HTRS 450kV/18000kVA Dual-Voltage Resonant Test System
Dual-Voltage Configuration
Parameter | 450kV Mode | 70kV Mode |
---|---|---|
Rated Capacity | 18000kVA | 2800kVA |
Rated Current | 40A | 40A |
Inductance Range | 35.82H-338.1H | 5.57H-52.6H |
Load Range | 30nF-283nF | 192.8nF-1820nF |
Performance Characteristics
Ultra-High Capacity: 18000kVA at 450kV
Precision Measurement:
Waveform distortion ≤1%
Noise level ≤75dB
Exceptional Efficiency:
Quality factor >50 (no load)
Quality factor >40 (under load)
Safety & Reliability
Capability | Condition | Duration |
---|---|---|
Overcurrent | 110% (44A) | 300 seconds |
Overvoltage | 110% (495kV) | 60 seconds |
Partial Discharge | Rated voltage | <2pC |
Mechanical Design
Core Technology
Adjustable iron coil structure:
9.4:1 inductance adjustment ratio (450kV mode)
9.4:1 inductance adjustment ratio (70kV mode)
Advanced materials:
Dual epoxy resin insulated tubes
1Ni18T9 non-magnetic stainless steel
Enclosure System
Tank-type construction:
Thermal management:
ONAN cooling system
ΔT ≤65K (winding), ≤55K (oil)
20kPa pressure-rated seals | Aeronautical acrylate gaskets |
Operational Parameters
Duty Cycle
Rated Load: 1 hour ON / 3 hours OFF
Daily Cycles: ≤6 maximum
Typical Applications
UHV transformer frequency testing
Extra high voltage cable validation
GIS partial discharge measurement
High-capacity capacitor bank testing
Quality Assurance
Factory testing includes:
Step-up voltage verification to 495kV
Partial discharge calibration
Thermal imaging validation
Complies with:
IEC 60270 (Partial Discharge)
IEEE Std 4 (High-Voltage Testing)