Tank Type
HTRS 200kV/2500kVA Multi-Range Resonant Reactor
Three-Voltage Configuration System
Output Voltage | Rated Current | Inductance Range | Load Capacitance |
---|---|---|---|
200kV | 12.5A | 50H-845H | 0.012μF-0.2μF |
100kV | 25A | 12.8H-253H | 0.04μF-0.79μF |
30kV | 83A | 1.15H-23H | 0.45μF-8.8μF |
Key Performance Parameters
Precision Measurement:
Frequency accuracy: 50Hz±1Hz
Harmonic distortion: -20° to +40° phase angle
Partial Discharge: ≤20pC at 200kV
Quality Factor: Adjustable 20-100 range
Continuous Operation: 1 hour at rated load
Physical Specifications
Dimensions (L×W×H) | 1900×2100×2400mm (3300mm incl. bushings) |
Weight | 12,700kg |
Cooling System | ONAN (Oil Natural Air Natural) |
Insulation Medium | 25# transformer oil (110kV grade) |
Advanced Mechanical Design
Core Technology
Adjustable iron coil structure with precision gaps
Dual epoxy resin insulated tubes
Eddy-current reduced stainless steel (1Ni18T9) components:
Non-magnetic guide rails
Double lead screw adjustment system
Enclosure System
Tank-type construction with sky blue anti-corrosion coating
Aviation-grade acrylate sealing:
Pressure tested to 20kPa
Thermal stable to 180°C
Flanged terminal connections for secure HV coupling
Thermal Management
Heat Dissipation:
Optimized radiator fin design
Thermal expansion-compensated oil reservoir
Operating Environment: -20°C to +40°C ambient
Typical Test Applications
Extra High Voltage (EHV) cable testing
Power transformer frequency response analysis
GIS partial discharge measurement
High-voltage capacitor bank validation
Quality Certification
Factory acceptance tests include:
72-hour continuous load test
Lightning impulse withstand verification
Partial discharge calibration at all voltage ranges
Compliant with IEC 60270 and IEEE Std 4