Tank Type
HTRS 300kV/3500kVA Ultra High Voltage Resonant System
Electrical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 3500kVA |
Output Voltage | 300kV |
Output Current | 11.7A |
Frequency | 50Hz ±1% |
Inductance Range | 81.6H - 800H |
Max Load Capacitance | 0.12μF (with divider) |
Performance Highlights
Exceptional Efficiency: Quality factor >60
Precision Measurement: Waveform distortion ≤1%
Low Noise Operation: ≤75dB at rated load
Wide Inductance Range: 10:1 adjustment ratio
Safety & Reliability
Capability | Condition | Duration |
---|---|---|
Overcurrent | 110% (12.87A) | 300 seconds |
Overvoltage | 110% (330kV) | 60 seconds |
Mechanical Design
Core Technology
Precision adjustable iron coil structure:
±1% linearity across full range
Dual epoxy resin insulated tubes
Advanced eddy-current prevention:
1Ni18T9 non-magnetic stainless steel
Double lead screw adjustment system
Enclosure System
Tank-type construction with:
Military-grade acrylate seals
Thermal management features:
ONAN cooling system
Expansion-compensated oil reservoir
20kPa pressure rating |
Operational Parameters
Duty Cycle
Rated Load: 1 hour ON / 1 hour OFF
Daily Cycles: ≤8 maximum
Thermal Limits
Winding temperature rise: ≤65K
Oil temperature rise: ≤55K
Typical Applications
EHV cable resonant frequency testing
400kV class transformer diagnostics
Ultra high voltage component validation
GIS partial discharge measurement
Quality Assurance
Factory acceptance tests include:
Step-up voltage verification to 330kV
Thermal imaging validation
Partial discharge calibration
Complies with:
IEC 60270 (Partial Discharge)
IEEE Std 4 (High-Voltage Testing)