High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Tank Type

HTRS 300kV/3500kVA Resonant Reactor - Ultra High Voltage Test System

Technical specifications for the HTRS 300kV/3500kVA resonant reactor featuring 81.6H-800H inductance range, 110% overvoltage capability, and aviation-grade sealing system.


  • US$ 117,284.00
  • Lead time: 120 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HTRS 300kV/3500kVA Ultra High Voltage Resonant System

Electrical Specifications

ParameterSpecification
Rated Capacity3500kVA
Output Voltage300kV
Output Current11.7A
Frequency50Hz ±1%
Inductance Range81.6H - 800H
Max Load Capacitance0.12μF (with divider)

Performance Highlights

  • Exceptional Efficiency: Quality factor >60

  • Precision Measurement: Waveform distortion ≤1%

  • Low Noise Operation: ≤75dB at rated load

  • Wide Inductance Range: 10:1 adjustment ratio

Safety & Reliability

CapabilityConditionDuration
Overcurrent110% (12.87A)300 seconds
Overvoltage110% (330kV)60 seconds

Mechanical Design

Core Technology

  • Precision adjustable iron coil structure:

    • ±1% linearity across full range

    • Dual epoxy resin insulated tubes

  • Advanced eddy-current prevention:

    • 1Ni18T9 non-magnetic stainless steel

    • Double lead screw adjustment system

Enclosure System

  • Tank-type construction with:

    • Military-grade acrylate seals

    • 20kPa pressure rating
  • Thermal management features:

    • ONAN cooling system

    • Expansion-compensated oil reservoir

Operational Parameters

Duty Cycle

  • Rated Load: 1 hour ON / 1 hour OFF

  • Daily Cycles: ≤8 maximum

Thermal Limits

  • Winding temperature rise: ≤65K

  • Oil temperature rise: ≤55K

Typical Applications

  1. EHV cable resonant frequency testing

  2. 400kV class transformer diagnostics

  3. Ultra high voltage component validation

  4. GIS partial discharge measurement

Quality Assurance

  • Factory acceptance tests include:

    • Step-up voltage verification to 330kV

    • Thermal imaging validation

    • Partial discharge calibration

  • Complies with:

    • IEC 60270 (Partial Discharge)

    • IEEE Std 4 (High-Voltage Testing)

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message