Tank Type
HTRS 60kV/775kVA Inductance Resonant Reactor Technical Overview
Product Introduction
The HTRS series resonant reactor is a precision-engineered solution for high-voltage testing applications requiring adjustable inductance and stable resonant characteristics. With three voltage taps (20kV, 40kV, 60kV) and wide inductance adjustment range, this 50Hz single-phase reactor meets demanding laboratory and industrial testing requirements.
Key Technical Specifications
Parameter | Tap 1 (20kV) | Tap 2 (40kV) | Tap 3 (60kV) |
---|---|---|---|
Rated Voltage | 20kV | 40kV | 60kV |
Rated Current | 38.75A | 19.375A | 12.9A |
Inductance Range | 32.86~1.643H | 131.48~6.574H | 296.2~14.81H |
Capacitor Load Range | 0.3086~6.173μF | 0.07714~1.543μF | 0.03424~0.6848μF |
Core Performance Metrics
Waveform Deviation: ≤1%
Quality Factor (Q): >40
Noise Level: ≤75dB at rated operation
Thermal Performance: Winding ΔT ≤65K, Oil ΔT ≤55K
Duty Cycle: 1 hour ON / 1 hour OFF (8 cycles/day at 100% rating)
Advanced Design Features
Magnetic Core Structure
Innovative iron coil design enables precise reactance adjustment through controlled air gap modification. The system incorporates:
Dual epoxy resin impregnated tubes
Eddy-current reduced stainless steel (1Ni18T9) brackets
Thermal expansion-compensated oil reservoir design
Mechanical Construction
The reactor features industrial-grade components for reliable operation:
Tank-type housing with impact-resistant flanges
20kPa pressure-rated sealing (aviation-grade acrylate gaskets)
Magnetic-field optimized stainless steel (1Ni18T9) guide rails
Double lead screw mechanism for noise-reduced iron coil adjustment
Safety & Environmental
Sky blue painted exterior for visual identification
Partial discharge-resistant terminal design
ONAN (Oil Natural Air Natural) cooling system
Typical Applications
This resonant reactor is ideal for:
Cable Testing: Frequency-tuned withstand voltage tests
Transformer Testing: Inductance-resonant diagnostic systems
GIS Testing: SF6 equipment quality verification
Research Labs: High-voltage component characterization
Operation & Maintenance
Installation Requirements
Minimum 1.5m clearance from grounded surfaces
Horizontal mounting on vibration-isolated base
Ambient temperature range: -25°C to +40°C
Maintenance Schedule
Monthly visual inspection of epoxy surfaces
Quarterly dielectric oil testing
Annual calibration of inductance adjustment mechanism
5-year major overhaul (including winding resistance measurement)
The HTRS 60kV/775kVA resonant reactor represents advanced engineering in high-voltage testing equipment, combining precise adjustable inductance with robust industrial construction for reliable operation in demanding electrical testing environments.