Tank Type
HTRS 60kV/3000kVA Inductance Resonant Reactor Technical Overview
Core Technical Parameters
Parameter | Specification |
---|---|
Rated Capacity | 3000kVA |
Input Voltage | 0.415kV ±10% |
Output Voltage | 60kV with 3kV taps |
Current Range | 1.25A~50A adjustable |
Load Capacitance | 0.0664-2.654μF |
Quality Factor (Q) | >40 |
Structural Design Features
Internal Construction
Core Material: 300130 orientation silicon steel with mitre joints
Winding Insulation: Epoxy glass cloth wrapped with inter-winding baffles
PD Level: <1pC at 100% rated voltage
External Protection
Enclosure: Tank-type with sky blue anti-corrosion coating
Sealing: 20kPa pressure tested, aviation-grade acrylate seals
Noise Level: <75dB during operation
Operational Specifications
Thermal Performance
Winding temperature rise: <65K at 100% load
Oil temperature rise: <55K (25# transformer oil)
Surface temperature rise: <30°C
Duty Cycle
100% UH/IH: 1hr ON / 1hr OFF (10 cycles max/day)
Continuous operation permitted at 80% rated voltage/current
Industrial Applications
This resonant test system is ideal for:
Cable withstand voltage testing (IEC 60502-2)
Gas-insulated switchgear (GIS) commissioning
Power transformer routine tests (IEC 60076)
Rotating machine insulation verification
Safety & Compliance
Meets IEC 60296 for insulating oil requirements
Stainless steel 1Ni18T9 non-magnetic components
Double lead screw design for vibration reduction
ONAN (Oil Natural Air Natural) cooling system