Tank Type
HTRS 60kV/2000kVA Inductance Resonant Reactor Technical Specifications
High-Capacity Resonant Testing Solution
The HTRS 60kV/2000kVA represents the industrial performance tier in adjustable resonant reactors, engineered for high-voltage equipment testing with exceptional stability (waveform deviation ≤1%) and ultra-low partial discharge (<5pc). this="" tank-type="" single-phase="" system="" accommodates="" test="" objects="" up="" to="" 1770nf="" capacitance="" across="" a="" 5.7h-150h="" inductance="" range.="">
Core Technical Parameters
Parameter | Specification |
---|---|
Rated Capacity | 2000kVA |
Voltage Range | 60kV (66kV over-voltage capable) |
Current Rating | 33.3A (39.96A overload) |
Inductance Range | 5.7H (min) - 150H (max) |
Test Object Capacitance | 1-1770nF |
Quality Factor (Q) | >40 |
Input Power | 380V±10%, 50Hz |
Critical Performance Benchmarks
Overload Capacity: 120% current (39.96A) for 600s | 110% voltage (66kV) for 60s
Thermal Limits: Δ65K winding | Δ55K oil temperature (1h ON/1h OFF ×8 cycles/day)
Precision: 1% reactance linearity (10-100% range) | Grade 1 measurement accuracy
Acoustics: ≤75dB at rated operation
Advanced Engineering Features
Patented Magnetic Design
Dual epoxy resin tubes with 1Ni18T9 austenitic stainless steel brackets
Eddy-current optimized magnetic circuit (Q>40 maintained)
Thermal expansion-compensated oil reservoir system
Precision Adjustment System
Motorized air gap adjustment (5-8 minute full travel)
Double lead screw mechanism with non-magnetic guides
Position limit protection at min/max air gaps
Lifting lugs for safe handling (800kg SWL)
Military-Grade Construction
20kPa pressure-rated tank (aviation acrylate seals)
Impact-resistant flanges (1500N·m torque rating)
Partial discharge-optimized terminals
MIL-STD-810G compliant vibration resistance
Protection & Safety Systems
Protection Type | Threshold | Response Time |
---|---|---|
Over-voltage | >66kV | <100ms<> |
Over-current | >39.96A | <500ms<> |
Flashover | dv/dt > 5kV/μs | <10μs<> |
Thermal | Winding >155°C | Instant |
Typical Test Applications
Power Equipment
GIS partial discharge tests
XLPE cable resonant withstand
Transformer induced voltage tests
Industrial Systems
Motor stator HV validation
Generator coil integrity checks
Switchgear dielectric verification
Installation Guidelines
Foundation: Level concrete pad (>300mm thickness) with M20 anchor bolts
Clearances: 2m radial / 3m vertical from grounded objects
Environment: Indoor (IP44) or weatherproof enclosure (IP54)
Commissioning: Dielectric oil test + 30min no-load run prior to service
Engineered for precision high-voltage testing laboratories and industrial facilities, the HTRS 60kV/2000kVA resonant reactor delivers unmatched stability through its military-grade construction and intelligent protection systems, complying with IEC 60270 (partial discharge) and IEC 60076 (reactor) standards.