Tank Type
HTRS 50kV/500kVA Adjustable Resonant Reactor
Design Standard: IEC 60060-1, GB1094, and IEC 1000 EMC compliant
Electrical Specifications
Parameter | Specification | Standard |
---|---|---|
Rated Capacity | 500 kVA | IEC 60076-6 |
Rated Voltage | 50 kVrms | IEC 60060-1 |
Rated Current | 10 A | |
Frequency | 50 Hz ±0.5% | IEC 60076-1 |
Inductance Range | 1:15 ratio (linearity ±1%) | GB/T 1094.10 |
Performance Characteristics
Electrical Performance
Quality Factor (Q): ≥10
Partial Discharge: <20pC @50kV
Waveform Distortion: ≤1% THD
Environmental
Noise Level: ≤65 dB(A)
Temperature Rise:
Winding: ≤65K
Oil: ≤55K
Mechanical Design
Core Adjustment System:
Dual 1Ni18T9 stainless steel lead screws
Precision rail guidance (0.05mm repeatability)
15:1 inductance adjustment range
Tank Construction:
20kPa pressure-rated enclosure
Aviation-grade acrylate seals (-40°C to 120°C)
Sky blue anti-corrosion coating
Cooling System:
ONAN (Oil Natural Air Natural)
Thermal modeling optimized airflow
Protection & Safety
Protection Type | Threshold | Duration |
---|---|---|
Overcurrent | 110% (11A) | 300s |
Overvoltage | 110% (55kV) | 60s |
Thermal | 65K winding ΔT | Automatic shutdown |
Operational Protocol
Duty Cycle:
1 hour ON / 1 hour OFF at 100% rating
Maximum 8 cycles per day
Inductance Adjustment:
Verify zero current before adjustment
Use manual crank for fine tuning
Pre-Test Checks:
Oil level verification
Grounding continuity test