Tank Type
HTRS 36kV/360kVA Dual-Function Resonant Reactor
Operation Modes: Adjustable resonant mode / Fixed inductance test transformer mode
Electrical Specifications
Parameter | Specification | Standard |
---|---|---|
Rated Capacity | 360 kVA | IEC 60076-6 |
Input Voltage | 400 Vrms | IEC 60214-1 |
Input Current | 50 A max | |
Output Voltage | 36 kVrms (40kV peak) | IEC 60060-1 |
Output Current | 0.5-10 A continuously adjustable | IEC 60076-1 |
Adjustable Parameters
Resonant Characteristics
Frequency: 50 Hz ±0.2%
Capacitance Range: 44.23-884.6 nF
Impedance Range: 3.6-72 kΩ
Performance Metrics
Quality Factor (Q): ≥220
Waveform Distortion: ≤0.5% THD
Partial Discharge: <5pC @36kV
Mechanical Design
Core Adjustment System:
Dual lead screw mechanism (1Ni18T9 stainless steel)
Air gap range: 0-150mm (upper/lower limit switches)
Position repeatability: ±0.1mm
Tank Construction:
20kPa pressure tested enclosure
Aviation-grade acrylate sealing rings
Oil level gauge and sampling ports
Cooling System:
ONAN cooling (China #25 oil)
65K max winding ΔT
55K max oil ΔT
Dual-Function Operation
Mode | Configuration | Applications |
---|---|---|
Resonant Mode | Adjustable air gap (0-150mm) | AC resonant testing |
Test Transformer Mode | Zero gap configuration | DC withstand testing |
Transition: Automatic gap position memory when switching modes
Protection & Safety
Overcurrent Protection: 120% for 180s (12A → 14.4A)
Overvoltage Protection: 110% for 60s (36kV → 40kV)
Insulation Monitoring: 5kV/min LV-ground withstand
Emergency Features:
Automatic discharge
Oil temperature cutoff