Tank Type
HTRS 140kV/420kVA Precision Resonant Reactor
Core Specifications
Electrical Parameters | |
---|---|
Rated Voltage | 140kV |
Rated Current | 3A (Max 3.3A) |
Frequency | 50Hz |
Inductance Range | 135.1H - 1690.4H |
Load Capacitance | 75.1pF - 6nF (incl. divider/coupling cap) |
Performance Highlights
Exceptional Stability:
Waveform distortion ≤1%
Noise level <75dB
Quality factor >50
Advanced PD Control: <2pC at 100% UH
Thermal Management:
Winding ΔT ≤65K
Oil ΔT ≤55K
Robust Safety Features
Test | Requirement | Duration |
---|---|---|
Overcurrent | 110% rated current | 300 seconds |
Overvoltage | 110% UH | 60 seconds |
Pressure | 20kPa sealing | No leakage |
Mechanical Design
Core Construction
Adjustable iron coil structure with ±1% linearity
Dual epoxy resin insulated tubes
Non-magnetic 1Ni18T9 stainless steel components:
Guide rails
Double lead screw adjustment system
Enclosure System
Tank-type sky blue housing
Military-grade acrylate sealing rings:
Oil-resistant formulation
Thermal stability to 180°C
Flanged terminal connections
Operational Parameters
Duty Cycle
Rated Load: 1 hour ON / 3 hours OFF
Daily Cycles: 6 maximum
Ambient Temp: -30°C to +50°C
Cooling System
ONAN (Oil Natural Air Natural) cooling with:
Optimized radiator fin design
Thermal expansion-compensated oil reservoir
Typical Applications
HV cable resonant frequency testing
Transformer winding diagnostics
GIS partial discharge measurement
High-voltage capacitor validation
Quality Assurance
Factory acceptance tests include:
72-hour heat run test
Step-up voltage verification
Partial discharge calibration
3-year warranty on core components