High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Tank Type

HTRS 120kV/3000kVA Resonant Test Reactor - 50Hz High-Voltage Testing System

Technical specifications for the HTRS 120kV/3000kVA resonant reactor featuring 611.5H-15.28H adjustable reactance, <1pC partial discharge, and ONAN cooling system.


  • US$ 67,752.00
  • Lead time: 120 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HTRS 120kV/3000kVA Resonant Test Reactor

Product Overview

This tank-type single-phase resonant reactor is designed for 50Hz high-voltage testing applications, featuring precision reactance adjustment from 611.5H to 15.28H with exceptional <1pC partial discharge performance.

Key Technical Specifications

ParameterSpecification
Rated Capacity3000kVA
Input Voltage0.415kV
Output Voltage120kV (with 6kV taps)
Current Range0.65A~25A
Load Capacitance0.0166~0.663μF

Performance Characteristics

  • Ultra-Low PD: <1pC at 100% UH (complete system)

  • Precision Waveform: ≤1% deviation with <70dB noise

  • Thermal Stability:

    • Winding temp rise ≤65K

    • Oil surface temp rise ≤55K

    • External temp rise ≤30°C

  • Quality Factor: >40 at rated conditions

Operational Duty Cycle

Operation ModeDurationCooling PeriodDaily Cycles
100% UH/IH1 hour ON1 hour OFF10 cycles max
80% UH/IHContinuous operation permitted

Advanced Structural Design

Internal Construction

  • Core material: 300130 orientation silicon steel sheets

  • Miter-cut joints with epoxy glass cloth wrapping

  • Multi-layer baffle insulation between windings/coils

  • Dual grounding system for safety

External Features

  • Pressure-tested tank structure (20kPa)

  • Aeronautical-grade sealing rings:

    • Oil-resistant composition

    • High-temperature stability (up to 150°C)

  • China GB 2536-2011 #25 transformer oil

Testing Capabilities

Ideal for precision high-voltage applications:

  1. XLPE cable resonant withstand testing

  2. Gas-insulated switchgear (GIS) diagnostics

  3. Transformer frequency response analysis

  4. High-voltage capacitor validation

Quality Assurance

  • Factory acceptance tests include:

    • 72-hour heat run test

    • Partial discharge measurement

    • Lightning impulse verification

  • 3-year warranty on core components

Installation Requirements

  • Minimum clearance: 2.5m radial, 4m vertical

  • Foundation load capacity: ≥8000kg

  • Ambient temperature range: -25°C to +40°C

>>>WhatsApp Communication<<<