Tank Type
HTRS 120kV/3000kVA Resonant Test Reactor
Product Overview
This tank-type single-phase resonant reactor is designed for 50Hz high-voltage testing applications, featuring precision reactance adjustment from 611.5H to 15.28H with exceptional <1pC partial discharge performance.
Key Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 3000kVA |
Input Voltage | 0.415kV |
Output Voltage | 120kV (with 6kV taps) |
Current Range | 0.65A~25A |
Load Capacitance | 0.0166~0.663μF |
Performance Characteristics
Ultra-Low PD: <1pC at 100% UH (complete system)
Precision Waveform: ≤1% deviation with <70dB noise
Thermal Stability:
Winding temp rise ≤65K
Oil surface temp rise ≤55K
External temp rise ≤30°C
Quality Factor: >40 at rated conditions
Operational Duty Cycle
Operation Mode | Duration | Cooling Period | Daily Cycles |
---|---|---|---|
100% UH/IH | 1 hour ON | 1 hour OFF | 10 cycles max |
80% UH/IH | Continuous operation permitted |
Advanced Structural Design
Internal Construction
Core material: 300130 orientation silicon steel sheets
Miter-cut joints with epoxy glass cloth wrapping
Multi-layer baffle insulation between windings/coils
Dual grounding system for safety
External Features
Pressure-tested tank structure (20kPa)
Aeronautical-grade sealing rings:
Oil-resistant composition
High-temperature stability (up to 150°C)
China GB 2536-2011 #25 transformer oil
Testing Capabilities
Ideal for precision high-voltage applications:
XLPE cable resonant withstand testing
Gas-insulated switchgear (GIS) diagnostics
Transformer frequency response analysis
High-voltage capacitor validation
Quality Assurance
Factory acceptance tests include:
72-hour heat run test
Partial discharge measurement
Lightning impulse verification
3-year warranty on core components
Installation Requirements
Minimum clearance: 2.5m radial, 4m vertical
Foundation load capacity: ≥8000kg
Ambient temperature range: -25°C to +40°C