HTRS Series Resonant Reactor - 120kV/2400kVA High-Voltage Testing Solution
Product Overview
The HTRS 120kV/2400kVA tank-type resonant reactor provides precision inductance adjustment for high-voltage frequency testing applications. Designed for 60Hz indoor use with three voltage configurations (60kV/75kV/120kV).
Core Technical Parameters
Parameter | Tap 1 | Tap 2 | Tap 3 |
---|---|---|---|
Rated Voltage | 60kV | 75kV | 120kV |
Rated Current | 40A | 32A | 20A |
Inductance Range | 3.98H-79.6H | 6.22H-124.4H | 15.92H-318.4H |
Performance Characteristics
Precision Waveform: ≤1% deviation with noise levels <75dB
Thermal Stability: Winding temp ≤65K, oil temp ≤55K rise
Quality Factor: ≥40 at rated conditions
Partial Discharge: <20pC standard (customizable)
Duty Cycle Specifications
Voltage Tap | Operation Time | Rest Period | Daily Cycles |
---|---|---|---|
60kV | 5 minutes ON | 1 minute OFF | 30 cycles |
75kV | 5 minutes ON | 1 minute OFF | 20 cycles |
120kV | 30 minutes ON | 30 minutes OFF | 10 cycles |
Structural Design Features
Mechanical Construction
Tank-type housing with sky blue anti-corrosion coating
Stainless steel (1Ni18T9) non-magnetic guide rails
Double lead screw iron coil adjustment system
20kPa pressure-tested aviation-grade acrylate seals
Electrical Insulation
HV winding withstand: 132kV/1min
Coupling terminal withstand: 10kV/1min
Epoxy resin insulated coil structure
Safety Compliance
The HTRS reactor meets stringent operational requirements:
Overcurrent: 110% rated current for 300s without damage
Overvoltage: 110% rated voltage for 60s without insulation failure
Cooling: ONAN (Oil Natural Air Natural) system
Applications
Ideal for:
Cable and transformer frequency withstand testing
GIS equipment resonance verification
High-voltage component quality validation
Maintenance Requirements
Annual dielectric strength verification
Quarterly inductance calibration
Monthly visual inspection for oil leaks