Tank Type
HTRS 100kV/500kVA Single-Phase Resonant Reactor
Electrical Characteristics
Parameter | Value | Test Standard |
---|---|---|
Rated Voltage | 100kV (+10% overload capability) | IEC 60060-1 |
Rated Current | 5A (5.5A for 300s) | IEEE C57.12.00 |
Frequency | 50Hz ±0.5% | IEC 61000-4-30 Class A |
Inductance Range | 1:15 adjustable ratio | GB/T 16927.1 |
Performance Metrics
Dielectric Strength
Partial Discharge: <20pC at 100kV
Overvoltage: 110kV for 60s
Waveform Distortion: ≤1% THD
Thermal Limits
Winding ΔT: ≤65K (IEC 60076-2)
Oil ΔT: ≤55K (25# mineral oil)
Duty Cycle: 1h ON/1h OFF (8 cycles/day)
Mechanical Design
Core Components
Adjustment Mechanism: Motorized air gap control with 1Ni18Cr9Ti guide rails
Noise Control: Double lead screw system (≤65dB at 1m)
Cooling: ONAN (Oil Natural Air Natural)
Enclosure Specifications
Pressure Test: 20kPa leak-proof (GB/T 7354)
Seals: Aviation acrylate (MIL-R-25988)
Coating: Sky blue epoxy (ISO 12944 C4)
Testing Capabilities
Compatible Test Objects
Power cable withstand testing (up to 35kV class)
GIS busbar partial discharge detection
Transformer turn-to-turn insulation verification
Protection Systems
Automatic over-current trip at 110% IH
Real-time PD monitoring interface
Air gap position interlock
Technical Highlights
Precision Engineering
Linearity: ±1% reactance error (10-100% range)
Q Factor: ≥10 at rated frequency
Eddy Current Loss: <0.5% via stainless steel construction
Reliability Features
Thermal expansion compensation design
Magnetic field-optimized pedestal
Epoxy-glass reinforced winding tubes