Tank Type
HTRS 100kV/2250kVA (75kV) Resonant Reactor
Voltage Tap Specifications
Parameter | 75kV Tap | 100kV Tap |
---|---|---|
Rated Current | 30A | 22.5A |
Inductance Range | 6.635H–132.7H | 11.8H–235.9H |
Load Capacitance | 53,077pF–1,061,542pF | 29,857pF–596,892pF |
Adjustment Ratio | 20:1 |
Technical Parameters
Electrical Performance
Frequency: 60Hz ±0.5%
Capacity: 2250kVA
THD: ≤1% (IEC 61000-4-7)
Dielectric Properties
Q Factor: ≥40
PD Level: <2pC @100% UH
Insulation: 10kV/min (HV to ground)
Enhanced Reliability
Overload Capability
Current: 120% (36A/27A) for 5min
Voltage: 110% withstand for 1min
Thermal Management
Winding ΔT: ≤65K (IEC 60076-2)
Oil ΔT: ≤55K
Duty Cycle: 1h ON/1h OFF (4×/day)
Precision Engineering
Core Components
Adjustment System: 20:1 air gap control
Material: 1Ni18Cr9Ti non-magnetic stainless
Noise: ≤75dB (Double lead screw)
Enclosure
Pressure Test: 20kPa (GB/T 7354)
Seals: MIL-R-25988 compliant
Coating: RAL 5015 sky blue
Certifications
IEC 60060-1 (High-voltage testing)
IEC 60270 (Partial discharge)
IEEE C57.12.90 (Temperature rise)