Tank Type
HTRS 100kV/1500kVA (75kV/50kV) Resonant Reactor
Multi-Voltage Operating Modes
Voltage | Current | Inductance Range | Load Capacitance |
---|---|---|---|
50kV | 30A | 4.6H ~ 95H | 0.012μF ~ 0.4μF |
75kV | 20A | 10H ~ 200H | 0.035μF ~ 0.7μF |
100kV | 15A | 17H ~ 587H | 0.075μF ~ 1.5μF |
Technical Specifications
Electrical Performance
Frequency: 60Hz ±0.5%
Q Factor: 20-100 adjustable
Waveform THD: ≤1% (IEC 61000-4-7)
Environmental
Noise Level: ≤75dB at 1m
Cooling: ONAN (Oil Natural Air Natural)
Insulation Oil: 25# mineral (IEC 60296)
Reliability Engineering
Overload Capability
Current: 110% rated for 300s
Voltage: 110% rated for 60s
PD Level: ≤2pC at 100% UH
Thermal Limits
Winding ΔT: ≤65K (IEC 60076-2)
Oil ΔT: ≤55K
Duty Cycle: 1h ON/3h OFF (6×/day)
Structural Design
Core Components
Adjustment System: Motorized air gap control
Frame Material: 1Ni18Cr9Ti non-magnetic stainless
Noise Control: Double lead screw mechanism
Enclosure
Pressure Test: 20kPa (GB/T 7354)
Seals: Aviation-grade acrylate
Coating: Sky blue epoxy (ISO 12944 C4)
Certifications & Standards
IEC 60060-1 (High-voltage testing)
IEC 60270 (Partial discharge measurement)
IEEE C57.12.90 (Temperature rise limits)