Cylinder Type
HCRS 800kV/6400kVA Inductance Resonant Reactor Technical Specifications
Product Overview
The HCRS 800kV/6400kVA cylinder-type single-phase resonant reactor sets new standards in high-voltage testing equipment. Featuring ONAN cooling and exceptional ≤2pC partial discharge performance at 100% UH, this system delivers reliable operation with 60-year engineered lifespan.
Technical Parameters
Parameter | Specification |
---|---|
Rated Capacity | 6400kVA |
Voltage Configuration | Single module: 400kV | Series connection: 800kV |
Frequency | 50Hz |
Current Range | 0-8A (8.8A overload for 300s) |
Cooling Method | ONAN (Oil Natural Air Natural) |
Quality Factor | ≥50 |
Partial Discharge | ≤2pC at 100% UH |
Temperature Rise | Winding ≤65K | Oil ≤55K | Surface ≤30K |
Performance Features
Robust Electrical Characteristics
110% overvoltage capability (880kV for 60s)
Waveform distortion ≤1.5%
Linearity: 10%-100% reactance with ≤1% error
No-load current
<10%<>
Advanced Mechanical Design
Dual epoxy resin tubes with stainless steel brackets
Thermal-expansion compensated oil system
Precision guide rail system for core adjustment
Noise-optimized design (≤70dB)
Core Innovations
Grain-Oriented Steel Core
1130-0-130 grade electrical steel with chip-removal treatment and curing agent integration for reduced eddy currents and 60-year operational life
Enhanced Grounding System
Reliable earthing baffles between windings and iron core ensure stable operation at 800kV
Thermal Management
Magnetic field-optimized pedestal design with three-tier temperature control (winding/oil/surface)
Operational Parameters
Operating Mode | Duration | Conditions |
---|---|---|
Full Load | 60 minutes | 100% UH (800kV), 100% IH (8A) |
Continuous Operation | Unlimited | 2/3 UH (533kV), 2/3 IH (5.3A) |
Overload Capacity | 300 seconds | 110% IH (8.8A) |
Quality Assurance
University-Validated Design: Developed with leading electrical engineering research institutes
Rigorous Testing: Each unit undergoes 72-hour burn-in testing at varying loads
Precision Manufacturing: Laser-aligned core gaps ensure consistent reactance adjustment
Performance Certification: Complies with IEC 60296 for insulating oils and IEC 60076 for power transformers
Typical Applications
XLPE cable AC withstand voltage testing
Gas-insulated substation (GIS) commissioning tests
Power transformer factory acceptance testing
High-voltage capacitor bank evaluation
Renewable energy grid connection equipment validation