HCRS 800kV/6400kVA Inductance Resonant Reactor Technical Specifications

Product Overview

The HCRS 800kV/6400kVA cylinder-type single-phase resonant reactor sets new standards in high-voltage testing equipment. Featuring ONAN cooling and exceptional ≤2pC partial discharge performance at 100% UH, this system delivers reliable operation with 60-year engineered lifespan.

Technical Parameters

ParameterSpecification
Rated Capacity6400kVA
Voltage ConfigurationSingle module: 400kV | Series connection: 800kV
Frequency50Hz
Current Range0-8A (8.8A overload for 300s)
Cooling MethodONAN (Oil Natural Air Natural)
Quality Factor≥50
Partial Discharge≤2pC at 100% UH
Temperature RiseWinding ≤65K | Oil ≤55K | Surface ≤30K

Performance Features

Robust Electrical Characteristics

  • 110% overvoltage capability (880kV for 60s)

  • Waveform distortion ≤1.5%

  • Linearity: 10%-100% reactance with ≤1% error

  • No-load current

    <10%<>

Advanced Mechanical Design

  • Dual epoxy resin tubes with stainless steel brackets

  • Thermal-expansion compensated oil system

  • Precision guide rail system for core adjustment

  • Noise-optimized design (≤70dB)

Core Innovations

Grain-Oriented Steel Core

1130-0-130 grade electrical steel with chip-removal treatment and curing agent integration for reduced eddy currents and 60-year operational life

Enhanced Grounding System

Reliable earthing baffles between windings and iron core ensure stable operation at 800kV

Thermal Management

Magnetic field-optimized pedestal design with three-tier temperature control (winding/oil/surface)

Operational Parameters

Operating ModeDurationConditions
Full Load60 minutes100% UH (800kV), 100% IH (8A)
Continuous OperationUnlimited2/3 UH (533kV), 2/3 IH (5.3A)
Overload Capacity300 seconds110% IH (8.8A)

Quality Assurance

  1. University-Validated Design: Developed with leading electrical engineering research institutes

  2. Rigorous Testing: Each unit undergoes 72-hour burn-in testing at varying loads

  3. Precision Manufacturing: Laser-aligned core gaps ensure consistent reactance adjustment

  4. Performance Certification: Complies with IEC 60296 for insulating oils and IEC 60076 for power transformers

Typical Applications

  • XLPE cable AC withstand voltage testing

  • Gas-insulated substation (GIS) commissioning tests

  • Power transformer factory acceptance testing

  • High-voltage capacitor bank evaluation

  • Renewable energy grid connection equipment validation