Cylinder Type
HCRS 1600kV/4000kVA Cylindrical Resonant Reactor System
Dual-Stage Operation Modes
Configuration | Rated Voltage | Max Current | Capacity | Insulation Level |
---|---|---|---|---|
Single Stage | 400kV | 2.5A | 1000kVA | 440kV/1min |
Two Stages | 1600kV | 2.5A | 4000kVA | 1760kV/1min |
Key Performance Indicators
Waveform Purity: ≤1% THD (IEC 60060-2 compliant)
Partial Discharge: <5pC @100% rated voltage
Quality Factor: Q>50 @50Hz
Measurement Accuracy: Class 1 (0.5% reading)
Noise Level: ≤70dB @1m (ONAN cooling)
Robust Thermal Design
Operating Condition | Temperature Rise Limit | Duty Cycle |
---|---|---|
100% Rated Current (2.5A) | Winding: ≤65K Oil: ≤55K Surface: ≤30K | 1hr ON/1hr OFF (6 cycles/day) |
120% Overcurrent (3A) | 300 seconds continuous |
Advanced Protection System
Triple-Layer Safeguards
Electrical Protection: Over-voltage (110% withstand for 60s) + Over-current + Flashover detection
Mechanical Protection: Air gap limit switches with guide rail system
Thermal Protection: Winding/oil temperature monitoring
Engineering Innovations
Magnetic Core Design
Material: 30-0-130 grain-oriented electrical steel
Noise Control: Chip-removed cores with polymer curing (≤70dB)
Adjustability: Precision air gap adjustment (vertical/horizontal)
Structural Features
Dual epoxy resin tubes with stainless steel brackets
Grounding shields between windings and core
Thermal expansion compensation for oil system
60+ years design life with 200,000 operations
Typical Applications
GIS Testing: 420kV~1100kV gas-insulated switchgear
Transformer Tests: Power transformer routine and type tests
Cable Testing: XLPE cable systems up to 500kV
Generator Testing: Stator winding insulation evaluation
Design Note: The cylindrical structure with adjustable air gap (0-300mm range) enables precise impedance matching for different test objects while maintaining Q factor >50 across all operating modes.
Certification & Compliance
IEC 60270 Partial Discharge Standard
IEEE Std 4-2013 High-Voltage Testing
GB/T 16927.1-2011 Lightning Impulse Test
CE Certified (EN 61010-1 Safety Requirements)