High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Cylinder Type

HCRS 1600kV/4000kVA Cylindrical Resonant Reactor - Technical Specifications for Ultra-High Voltage Testing

Complete technical specifications of HCRS 1600kV/4000kVA cylindrical resonant reactor with dual-stage configuration for ultra-high voltage equipment testing.


  • US$ 465,043.00
  • Lead time: 120 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HCRS 1600kV/4000kVA Cylindrical Resonant Reactor System

Dual-Stage Operation Modes

ConfigurationRated VoltageMax CurrentCapacityInsulation Level
Single Stage400kV2.5A1000kVA440kV/1min
Two Stages1600kV2.5A4000kVA1760kV/1min

Key Performance Indicators

  • Waveform Purity: ≤1% THD (IEC 60060-2 compliant)

  • Partial Discharge: <5pC @100% rated voltage

  • Quality Factor: Q>50 @50Hz

  • Measurement Accuracy: Class 1 (0.5% reading)

  • Noise Level: ≤70dB @1m (ONAN cooling)

Robust Thermal Design

Operating ConditionTemperature Rise LimitDuty Cycle
100% Rated Current (2.5A)Winding: ≤65K
Oil: ≤55K
Surface: ≤30K
1hr ON/1hr OFF (6 cycles/day)
120% Overcurrent (3A)300 seconds continuous

Advanced Protection System

Triple-Layer Safeguards

  1. Electrical Protection: Over-voltage (110% withstand for 60s) + Over-current + Flashover detection

  2. Mechanical Protection: Air gap limit switches with guide rail system

  3. Thermal Protection: Winding/oil temperature monitoring

Engineering Innovations

Magnetic Core Design

  • Material: 30-0-130 grain-oriented electrical steel

  • Noise Control: Chip-removed cores with polymer curing (≤70dB)

  • Adjustability: Precision air gap adjustment (vertical/horizontal)

Structural Features

  • Dual epoxy resin tubes with stainless steel brackets

  • Grounding shields between windings and core

  • Thermal expansion compensation for oil system

  • 60+ years design life with 200,000 operations

Typical Applications

  • GIS Testing: 420kV~1100kV gas-insulated switchgear

  • Transformer Tests: Power transformer routine and type tests

  • Cable Testing: XLPE cable systems up to 500kV

  • Generator Testing: Stator winding insulation evaluation

Design Note: The cylindrical structure with adjustable air gap (0-300mm range) enables precise impedance matching for different test objects while maintaining Q factor >50 across all operating modes.

Certification & Compliance

  • IEC 60270 Partial Discharge Standard

  • IEEE Std 4-2013 High-Voltage Testing

  • GB/T 16927.1-2011 Lightning Impulse Test

  • CE Certified (EN 61010-1 Safety Requirements)

>>>WhatsApp Communication<<<