Cylinder Type
HCRS 1500kV/9000kVA Modular Resonant Test System
System Configuration Matrix
Connection Mode | Output Voltage | Current Rating | Inductance Range (H) | Load Range (nF) |
---|---|---|---|---|
Single Reactor | 500kV | 6A | 74-845.2 | 12-137 |
Two Serial | 1000kV | 6A | 148-1690.4 | 6-68.5 |
Three Serial | 1500kV | 6A | 222-25356 | 4-45.7 |
Two Parallel | 500kV | 12A | 37-422.5 | 24-274 |
Three Parallel | 500kV | 18A | 24.66-281.7 | 36-411.3 |
Key Performance Parameters
Partial Discharge: <10pC @1500kV, <2pC @1050kV
Waveform Distortion: ≤1.5% THD
Quality Factor: Q≥50 (standard), Q>40 (worst-case)
Noise Level: ≤70dB @5m distance
Insulation Withstand: 1650kV (110% rated) for 1min
Advanced Protection System
Triple-layer protection: Over-voltage/current + flashover + air gap limit
Automatic return-to-zero mechanism for air gap adjustment
Phase sequence detection with motor reversal protection
Real-time air gap monitoring via control console
Synchronized transmission across modules (±5% impedance matching)
Structural Innovations
Core Components
Magnetic Core: 30-0-130 grain-oriented steel with chip removal treatment
Noise Control: Curing agent integrated core assembly (≤70dB)
Cooling System: ONAN cooling with thermal expansion compensation
Modular Design Features
Quick-connect transmission shafts with backup protection
Standardized HV lead wire interfaces
Pre-aligned mounting bases for field assembly
Guide rail system for precise air gap adjustment
Operational Guidelines
Parameter | Specification |
---|---|
Input Power | 380V±10%, 50Hz (customizable) |
Continuous Operation | 60min @rated load (ΔT≤65K winding, ≤55K oil) |
Tuning Capability | Reaches resonance at 1-1.5kV excitation |
System Lifetime | 60+ years design life |
Quality Assurance
This system implements:
Impedance matching test (±5% deviation requirement)
72-hour burn-in test before shipment
Partial discharge calibration with 100pC reference
Third-party certification available (ASTA, KEMA, etc.)
Pro Tip: The system's wide inductance adjustment range (24.66-25356H) allows testing of various equipment from power transformers (typically 10-100nF) to long cables (0.1-1μF) with single setup.