Cylinder Type
HCRS 1500kV/5250kVA Resonant Test System Specifications
System Configuration Options
Multi-stage operation flexibility:
Three-stage mode: 1500kV/3.5A output
Two-stage mode: 1000kV/3.5A output
Parallel mode: 500kV/7A output
Electrical Parameters
Primary Specifications | |
---|---|
Input Voltage | 0.44kV ±10% (Two-phase) |
Input Current | 284A at full load |
Quality Factor | Q≥45 @60Hz |
Frequency Range | 50Hz/60Hz switchable |
Waveform Distortion | <1% THD |
Measurement Accuracy | Class 1 (IEC 60060-2) |
Load Compatibility Matrix
Output Voltage | Load Capacitance | Configuration |
---|---|---|
1500kV | 6200pF | With voltage divider |
1000kV | 9300pF | With voltage divider |
500kV | 18566pF | Single-stage |
500kV | 37130pF | Parallel-stage |
Single-Stage Reactor (HCRS 500kV/1750kVA)
Nominal Inductance: Lmin=379H
Optimal Load: 18566pF (with divider)
Insulation Level: 550kV (1.1× rated) for 1min
Thermal Performance: ΔT≤65K (winding), ≤55K (oil)
Advanced Engineering Features
Core Material: 30-0-130 grain-oriented electrical steel
Adjustable Air Gap: Precision guide rail system for vertical/horizontal coil movement
Noise Reduction: Chip-removed steel cores with curing agent integration (≤70dB)
Thermal Management: Oil expansion compensation design
Structural Integrity: Dual epoxy tubes with stainless steel brackets
Operational Reliability
Duty Cycle: Continuous 1-hour operation at rated parameters
Extended Operation: Unlimited runtime at 2/3 rated capacity
Design Lifetime: 60+ years service life
Safety Compliance: Meets IEC 61010-1 & IEEE Std 4
Industry Applications
This system is ideal for:
Power transformer routine tests
GIS partial discharge measurement
XLPE cable withstand voltage testing
Generator stator insulation evaluation
Technical Note: The system's dual-frequency capability (50Hz/60Hz) and modular design allow adaptation to various international testing standards including IEC, ANSI, and GB requirements.