HCRS 1200kV/6000kVA 60Hz Resonant Test System - High-Capacity HV Testing Solution

The HCRS 1200kV/6000kVA resonant test system offers 5A output current at 1200kV, adjustable inductance (4696~723.8H), and ≤5pC partial discharge for industrial high-voltage testing applications.


  • US$ 327,869.00
  • Lead time: 120 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HCRS 1200kV/6000kVA 60Hz Resonant Test System

The HCRS 1200kV/6000kVA Inductance Resonant Reactor delivers exceptional 5A output capacity at 1200kV, featuring wide inductance adjustment (4696~723.8H) and industry-leading ≤5pC partial discharge performance for rigorous high-voltage testing applications.

Electrical Specifications

  • Input Voltage: 0.44kV ±5% (Two-phase a/b 440V)

  • Frequency: 60Hz

  • Output Voltage: 1200kV (Three reactors serial connection)

  • Output Current: 5A (Three reactors serial connection)

  • Configuration Options:

    • 1200kV @ 11053pF

    • 800kV @ 16579pF

    • 400kV @ 33158pF (all include divider)

  • Waveform Deviation: <1%

  • Measuring Accuracy: 1 grade

Performance Parameters

  • Inductance Range: 4696~723.8H

  • Quality Factor (Q): ≥45 (without water termination/resistance load)

  • Noise Level: ≤70dB (rated conditions, 4m distance)

  • Insulation: Withstands 1min at 1.1× rated voltage

  • Partial Discharge:

    • ≤5pC @ 100% Un

    • ≤3pC @ 80% Un

  • Breakdown Testing: Sustains 1100kV without system damage

Operational Modes

Standard Testing Cycle

  • 1 hour ON / 1 hour OFF @ rated voltage/current

  • Maximum 4 cycles per day

  • Continuous 3-hour operation @ 900kV

Extended Duty Cycle

  • 20-day continuous operation @ 600kV

  • Load capacitance: 13250pF (Two reactors serial connection)

Advanced Structural Design

  • Core Construction: Adjustable iron coil with precision gap tuning

  • Premium Materials:

    • 30-0-130 grain-oriented electrical steel

    • Stainless steel brackets with dual epoxy tubes

  • Thermal Management:

    • High-intensity magnetic field heat dissipation

    • Oil expansion/contraction compensation system

  • Noise Control Technology:

    • Chip-removed cured iron core

    • Precision guide rail system for smooth adjustment

  • Safety Systems:

    • Reliable grounding baffles between winding/iron core

    • Comprehensive protection (over-voltage, over-current, flashover)

    • Air gap limit monitoring

System Features

  • Linearity: 10%-100% reactance, error ≤±1%

  • Field Verification: Partial discharge testing at user facility

  • Design Lifespan: >60 years operational life

  • Technical Collaboration: Developed with leading research institutions

Conclusion

The HCRS 1200kV/6000kVA Resonant Test System sets new standards for high-current (5A) testing at 1200kV, with its exceptional 60Hz performance and flexible configuration options. The system's robust construction, precise inductance adjustment (4696~723.8H range), and comprehensive safety features make it ideal for demanding high-voltage testing applications requiring 6000kVA capacity.