Cylinder Type
HCRS 800kV/3200kVA Inductance Resonant Reactor Technical Overview
Product Description
The HCRS series 800kV/3200kVA inductance resonant reactor represents the cutting-edge in high-voltage testing equipment. This cylinder-type single-phase reactor features advanced design with grain-oriented electrical steel (1130-0-130 grade) and achieves exceptional partial discharge levels of <5pC at 800kV.
Key Specifications
Parameter | Specification |
---|---|
Rated Capacity | 3200kVA |
Voltage Configuration | Single resonant: 400kV | Series connection: 800kV |
Frequency Range | 50-120Hz |
Rated Current | 4A (with 4.8A overcurrent capability for 60s) |
Waveform Deviation | ≤1.5% |
Partial Discharge Level | <5pC at 800kV | <2pC at 550kV |
Temperature Rise | Oil surface ≤55K | Winding ≤65K |
Noise Level | ≤75dB |
Advanced Design Features
Structural Innovations
Iron core structure with adjustable air gaps
Dual epoxy resin tubes with stainless steel brackets to minimize eddy current losses
Thermally compensated design accounting for oil expansion/contraction
Guide rail system ensuring precise vertical/horizontal core movement
Protection Systems
Over-voltage protection (110% UH for 300s)
Over-current protection (120% IH for 60s)
Test object flashover protection
Air gap limit protection (max/min)
Performance Characteristics
Reliability Enhancements
The reactor incorporates multiple design improvements including:
Chip-removed steel treatment with curing agent integration for noise reduction
Reliable earthing baffles between winding and iron core
60-year minimum design life expectancy
Operational Parameters
Continuous operation: 60 minutes at 100% UH/IH
Extended operation capability at 2/3 rated voltage/current
Precision measurement system (Grade 1 accuracy)
Motorized inductance adjustment
Technical Advantages
Superior Insulation: Achieves industry-leading PD levels through optimized oil-impregnated paper insulation system
Thermal Management: Pedestal design dissipates heat from high-intensity magnetic fields
Precision Control: Electrical motor adjustment enables fine-tuning of inductance values
Research-Backed Design: Developed in collaboration with leading universities and research institutes
Applications
This high-performance resonant reactor is ideal for:
Cable withstand voltage testing
GIS (Gas Insulated Switchgear) testing
Transformer and reactor factory tests
High-voltage component qualification
Research laboratory applications
Quality Assurance
Every HCRS 800kV/3200kVA reactor undergoes rigorous testing including:
Partial discharge measurement at multiple voltage levels
Temperature rise verification under full load
Waveform distortion analysis
Protection system functional tests
72-hour continuous operation trial