High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Cylinder Type

HCRS 800kV/3200kVA Inductance Resonant Reactor - Technical Specifications & Features

Technical specifications of HCRS 800kV/3200kVA inductance resonant reactor with 50-120Hz frequency range, <5pC PD level at 800kV, and 60-year design life for high-voltage testing applications.


  • US$ 181,420.00
  • Lead time: 120 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HCRS 800kV/3200kVA Inductance Resonant Reactor Technical Overview

Product Description

The HCRS series 800kV/3200kVA inductance resonant reactor represents the cutting-edge in high-voltage testing equipment. This cylinder-type single-phase reactor features advanced design with grain-oriented electrical steel (1130-0-130 grade) and achieves exceptional partial discharge levels of <5pC at 800kV.

Key Specifications

ParameterSpecification
Rated Capacity3200kVA
Voltage ConfigurationSingle resonant: 400kV | Series connection: 800kV
Frequency Range50-120Hz
Rated Current4A (with 4.8A overcurrent capability for 60s)
Waveform Deviation≤1.5%
Partial Discharge Level<5pC at 800kV | <2pC at 550kV
Temperature RiseOil surface ≤55K | Winding ≤65K
Noise Level≤75dB

Advanced Design Features

Structural Innovations

  • Iron core structure with adjustable air gaps

  • Dual epoxy resin tubes with stainless steel brackets to minimize eddy current losses

  • Thermally compensated design accounting for oil expansion/contraction

  • Guide rail system ensuring precise vertical/horizontal core movement

Protection Systems

  • Over-voltage protection (110% UH for 300s)

  • Over-current protection (120% IH for 60s)

  • Test object flashover protection

  • Air gap limit protection (max/min)

Performance Characteristics

Reliability Enhancements

The reactor incorporates multiple design improvements including:

  • Chip-removed steel treatment with curing agent integration for noise reduction

  • Reliable earthing baffles between winding and iron core

  • 60-year minimum design life expectancy

Operational Parameters

  • Continuous operation: 60 minutes at 100% UH/IH

  • Extended operation capability at 2/3 rated voltage/current

  • Precision measurement system (Grade 1 accuracy)

  • Motorized inductance adjustment

Technical Advantages

  1. Superior Insulation: Achieves industry-leading PD levels through optimized oil-impregnated paper insulation system

  2. Thermal Management: Pedestal design dissipates heat from high-intensity magnetic fields

  3. Precision Control: Electrical motor adjustment enables fine-tuning of inductance values

  4. Research-Backed Design: Developed in collaboration with leading universities and research institutes

Applications

This high-performance resonant reactor is ideal for:

  • Cable withstand voltage testing

  • GIS (Gas Insulated Switchgear) testing

  • Transformer and reactor factory tests

  • High-voltage component qualification

  • Research laboratory applications

Quality Assurance

Every HCRS 800kV/3200kVA reactor undergoes rigorous testing including:

  • Partial discharge measurement at multiple voltage levels

  • Temperature rise verification under full load

  • Waveform distortion analysis

  • Protection system functional tests

  • 72-hour continuous operation trial