Cylinder Type
HCRS 800kV/1200kVA Dual-Voltage Resonant Reactor
Product Overview
The HCRS 800kV/1200kVA cylinder-type single-phase resonant reactor offers flexible dual-voltage testing capability (400kV/800kV) with motor-adjusted reactance control. This precision system delivers Q≥40 performance with partial discharge levels below 5pC at rated voltage, making it ideal for sensitive high-voltage testing applications.
Configuration Options
Single Stage Operation
Rated Voltage: 400kV
Rated Current: 1.5A
Dual Stage Series Connection
Rated Voltage: 800kV
Rated Current: 1.5A
Performance Specifications
Parameter | Specification |
---|---|
Rated Capacitance | 1200kVA |
Rated Frequency | 50Hz |
System Quality Factor (Q) | ≥40 |
Partial Discharge | <5pC @100% voltage <2pC @80% voltage |
Waveform Deviation | ≤1% |
Noise Level | ≤65dB |
Insulation Level | 1.5× rated voltage for 1min |
Adjustment Parameters
Parameter | Range |
---|---|
Reactance Adjusting | 0-260Ω |
Inductance Adjusting | Motor-controlled precision adjustment |
Load Capacitance | Configurable to test requirements |
Operational Parameters
Duty Cycle
30 minutes ON / 30 minutes OFF at rated voltage
Maximum 8 cycles per day
Continuous operation at 70% rated voltage
Thermal Performance
Winding Temperature Rise: ≤65K
Oil Temperature Rise: ≤55K
Advanced Features
Precision Adjustment System
Motor-controlled reactance adjustment
Guide rail system for accurate coil alignment
Real-time air gap monitoring
Protection Systems
Over-voltage and over-current protection
Test object flashover protection
Air gap limit protection (max/min)
Measurement accuracy: Grade 1
Core Construction
Grain-oriented electrical steel (130-0-130)
Chip-removal treatment with curing agent
Stainless steel brackets minimize eddy currents
Quality Assurance
60+ year design lifespan
University/research institute collaborations
Continuous quality improvements
Optimized structural design