Cylinder Type
HCRS 750kV/750kVA Dual-Voltage Resonant Reactor
Product Overview
The HCRS 750kV/750kVA cylinder-type single-phase resonant reactor offers flexible testing capabilities with both 375kV (single module) and 750kV (dual module) operation modes. This precision instrument delivers Q>40 performance with partial discharge levels below 5pC at full rated voltage, making it ideal for demanding high-voltage testing applications.
Configuration Options
Single Module Operation
Rated Voltage: 375kV
Rated Current: 1A (1.2A max)
Reactance Range: 375-1592.4kΩ
Dual Module Series Connection
Rated Voltage: 750kV
Reactance Range: 750-3184.7kΩ
Performance Specifications
Parameter | Specification |
---|---|
Rated Frequency | 50Hz |
Rated Capacity | 750kVA |
System Quality Factor (Q) | >40 |
Partial Discharge | <5pC @100% voltage <3pC @80% voltage |
Waveform Deviation | ≤1.5% |
Noise Level | ≤70dB |
Cooling Method | ONAN |
Unload Current | <10% |
Technical Parameters
Inductance Ranges
Single Module: 1194.3-5071.2H
Dual Module Series: 2388.5-10142.4H
Load Capacitance
Single Module: 8492.6-20,000pF (incl. divider)
Dual Module Series: 4246.4-10,000pF (incl. divider)
Robust Protection Systems
Overload Capabilities
Current: 1.2A (120%) for 300s - no thermal damage
Voltage: 825kV (110%) for 60s - no insulation damage
Additional Protection
Linearity: ±1% across 10-100% reactance range
Precision measurement system
Operational Parameters
Duty Cycle
Continuous operation at 2/3 rated voltage/current
60 minutes at 100% rating
Thermal Limits
Winding Temperature Rise: ≤65K
Oil Surface Temperature Rise: ≤55K
External Surface Temperature Rise: ≤30K
Advanced Design Features
Core Construction
Grain-oriented electrical steel (130-0-130)
Chip-removal treatment with curing agent
Noise reduction technology (≤70dB)
Adjustable Reactance System
Precision air gap adjustment
Stainless steel brackets minimize eddy current losses
Guide rail system for accurate coil alignment
Thermal Management
High-intensity magnetic field heat dissipation
Oil system thermal expansion compensation
Reliable grounding baffles between windings
Quality Assurance
60+ year design lifespan
Developed with leading research institutions
Continuous quality improvements
Optimized structural design