Cylinder Type
HCRS 650kV/6500kVA Inductance Resonant Reactor System
High-Voltage Testing Solution for Demanding Applications
This two-stage series-connected resonant reactor system delivers 6500kVA capacity at 650kV, designed for both laboratory and outdoor high-voltage testing applications. The modular design allows flexible configuration with exceptional partial discharge performance.
System Specifications
Electrical Parameters
Rated Capacity: 6500kVA
Voltage Configuration: 325kV/stage (2-stage)
Rated Current: 10A
Frequency: 50Hz
Performance Metrics
Partial Discharge: <2pC (lab), 50-100pC (field)
Waveform Deviation: ≤1.5%
Inductance Range: 125H-3000H
Quality Factor: >50
Robust Operational Capabilities
Overload Performance
Current: 110% (11A) for 600s - winding protected
Voltage: 110% (700kV) for 60s - insulation protected
Environmental Resilience
Verified outdoor operation up to 700kV
Weatherproof epoxy skirt design
Unaffected by rain or snow conditions
Single Reactor Module (HCRS325kV/3250kVA)
Configuration
Cylinder type, single phase
Cooling Method
ONAN
Noise Level
<70dB
No-load Current
<10%
Inductance Range
60H-1500H (rated load)
Advanced Engineering Features
Core Construction
30-0-130 grain-oriented electrical steel
Chip-removal treatment with curing agent
Precision guide rail adjustment system
Structural Advantages
Reliable winding-to-coil grounding baffles
60+ year design lifespan
Optimized for minimal noise emission
University-validated improvements
System Applications
Outdoor high-voltage equipment testing
Power transformer diagnostic tests
Cable and GIS partial discharge measurement
High-voltage component research
Transmission equipment qualification
Why Choose This Resonant System?
Proven track record (2250kV/2A systems delivered)
Exceptional field performance in harsh conditions
Industry-leading partial discharge characteristics
Precision-engineered variable inductance control
Academic collaboration ensuring technical excellence