Cylinder Type
HCRS 500kV/1000kVA Ultra High Voltage Test System
Flexible Operation Modes
Configuration | Inductance Range | Load Range | Reactance Range |
---|---|---|---|
Single Module | 398H-2535.6H | 4000-25483pF | 796.2kΩ-125kΩ |
Series Connection | 796H-5071.2H | 2000-12741pF | 1592.4kΩ-250kΩ |
Core Specifications
Parameter | Specification |
---|---|
Rated Capacity | 1000kVA |
Output Voltage | 500kV (550kV withstand) |
Rated Current | 2A (2.4A max) |
Quality Factor | ≥50 |
Performance Highlights
Ultra-Low PD: <2pC at 500kV
Record Inductance: Up to 5071.2H in series
Precision Measurement:
Waveform distortion ≤1.5%
1-grade accuracy
Safety & Protection
Capability | Condition | Duration |
---|---|---|
Overcurrent | 125% (2.4A) | 300 seconds |
Overvoltage | 110% (550kV) | 60 seconds |
Mechanical Design
Cylinder-Type Architecture
30-0-130 grain-oriented silicon steel core
Dual epoxy tube construction:
Stainless steel bracketing
±1% linearity
Noise Reduction Technology
Chip-removed steel treatment:
Curing agent integration
≤75dB operation
Precision guide rail system
Operational Parameters
Duty Cycle
Rated Load: 60 minutes continuous
Derated Operation: Unlimited at 80% rating
Thermal Limits:
Winding ΔT≤65K
Oil ΔT≤55K
Quality Assurance
Durability Features
60-year design life
University-developed core technology
Research institute collaboration
Testing Validation
Partial discharge verification
Thermal imaging validation
Mechanical endurance testing