High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Gas Insulated Divider

SF6 1250kV/500pF Capacitor Voltage Divider - Ultra-High Capacity Coupling & Measurement

1250kV/500pF SF6 gas-insulated divider with 4000:1 ratio and <0.2% dielectric loss. Dual-function design for UHV measurement and power line carrier communication.


  • US$1.00; Negotiated Price
  • Lead time: 120days

>>>WhatsApp Communication<<<

Product Details

Product Tags

SF6 1250kV/500pF Capacitor Voltage Divider - Ultra-High Capacity Coupling & Measurement

This 1250kV/500pF SF6 Capacitor Voltage Divider sets new benchmarks in ultra-high-voltage (UHV) technology, combining precision measurement (≤1% accuracy) with power line coupling functionality in a single gas-insulated unit. Its exceptional 500pF capacity enables simultaneous voltage monitoring and signal transmission in 1000kV+ systems.

Technical Specifications

ParameterSpecification
Rated Voltage1250kV (1312.5kV withstand for 60s)
Nominal Ratio4000:1 ±0.3%
Dielectric Loss<0.2% @20°C
Partial Discharge≤5pC @1250kV, ≤3pC @1000kV
Duty Cycle5min ON / 30min OFF (20 cycles/day max)

Dual-Functional Advantages

1. Precision Voltage Measurement

  • Industry-leading <+1% accuracy at 1250kV

  • Temperature-stable (<0.0005/°C coefficient)

  • 4000:1 ratio for sensitive instrumentation

2. High-Capacity Coupling

  • 500pF capacity enables 200kHz+ carrier signals

  • Low-loss design (<0.2%) maintains signal integrity

  • IEC 60358 compliant coupling performance

Engineering Breakthroughs

Extreme Voltage Performance

  • 105% overload capability (1312.5kV)

  • SF6 gas insulation prevents corona above 800kV

  • Conducting rod design minimizes inductance

Advanced Partial Discharge Control

  • ≤3pC sensitivity at 80% rated voltage

  • Shielded structure reduces external interference

  • Compatible with IEC 60270 measurement systems

Typical Applications

  • UHV Transmission Lines: 1000kV+ system monitoring

  • Converter Stations: HVDC valve hall measurements

  • Power Line Carrier: Protection signaling at 1250kV

  • Research Facilities: Dielectric testing up to 1312kV

Standards Compliance

  • IEC 61869-1/-2 (Instrument Transformers)

  • IEEE C37.100 (HV Testing Requirements)

  • GB/T 4109 (UHV Equipment Standards)

  • IEC 62271-303 (SF6 Handling)

Critical Operational Guidelines

  1. Strictly adhere to 5-minute operational periods

  2. Maintain 30-minute cooling intervals

  3. Maximum 20 activation cycles per 24-hour period

  4. SF6 gas pressure must remain at 0.45±0.05MPa

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message